Formulas
The same identities as the tools, grouped.
Air
CFM = ACH × Volume / 60ACH to CFMOpenrequired = max(50 CFM code floor, HVI area or fixtures, 8 ACH); buy next common fanBathroom fan CFMOpenQ = max(100 CFM, 100 or 150 CFM/ft × width, BTU/h ÷ 100); flag makeup air if Q > 400Range hood CFMOpenQ_vent = 0.03 A_floor + 7.5 (N_br + 1) (ASHRAE 62.2 form, IP)ASHRAE 62.2OpenV_bz = Rp × Pz + Ra × Az (ASHRAE 62.1 breathing-zone form)ASHRAE 62.1 OAOpenif Q_exh > 400 CFM then Q_mu ≈ Q_exh, else 0 (IRC talk; not Q_exh − 400)Makeup airOpenCFM = ACH × V / 60 or CFM = cfm/ft² × AGarage exhaustOpenA_net ≈ A_attic / 150 (or /300); split 50/50 intake/exhaust NFA in in²Attic ventilationOpenCFM = ACH_ISO × V / 60 (ACH from user ISO class pick or custom)Cleanroom ACHOpenQ = V × exchanges/min × (1 + filter%) × lights (1/min is the common tent sketch)Grow tent CFMOpenACH = CADR × 60 / V; also CADR_5ACH = V × 5 / 60CADR air changesOpenACH_nat ≈ ACH50 / N; CFM_nat ≈ CFM50 / N (N chips 20/16/13)ACH50 to ACHOpenCFM = ACH × V / 60 or CFM = cfm/ft² × AParking garage CFMOpenQ_sys = tons × CFM/ton; Q_room = Q_sys × (A×f) / Σ(A×f)CFM per roomOpenQ = n × CFM/unit or Q = A × CFM/ft² (user-typed rates)Commercial exhaust CFMOpenQ = L_hood × CFM/ft (wall canopy 200/300/400/550 by duty)Commercial kitchen hoodOpenQ_tot = dryer + hood + baths; makeup if hood>400 or dryer>200Dryer exhaust and makeupOpenCFM = A × (CFM/ft²) × (H/8); NFA = CFM/750; window = CFM/750Whole-house fanOpenCFM = (A × H) / minutes; 2 min = 30 ACH, 3 min = 20 ACHEvaporative coolerOpenCFM = attic floor × 0.7 (dark or steep × 0.805); intake = CFM / 300Attic fanOpenQ/person = G / ((C_in − C_out)/10^6)CO₂ to CFMOpenQ = 0.03 A + 7.5 (N_br + 1); q_recovered = 1.08 × Q × ΔT × εERV / HRV heatOpen
Duct
equal-friction d = (0.109136 × Q^1.9 / f)^(1/5.02); also A = Q/VDuct sizeOpenV = Q / ADuct velocityOpenDe = 1.30 (a b)^0.625 / (a + b)^0.25 (Huebscher)Equivalent round ductOpenΔP/L from user friction rate × length, or Darcy-Weisbach sketchDuct frictionOpenΔP = C × (ρ/2) V²Fitting lossOpenL_center = offset / sin θ; heel-throat from geometryDuct offsetOpenESP ≈ Σ ΔP_duct + Σ ΔP_fit + ΔP_coil/filter (user terms)Static pressureOpenΔP = f × TELTotal equivalent lengthOpenAR = a/b; area held, De from HuebscherDuct aspect ratioOpenACFM = SCFM × (T_act/T_std) × (P_std/P_act)SCFM to ACFMOpenρ = P / (R T) dry-air sketch; altitude optionalAir densityOpenA_free = Q / V_face; A_nominal = A_free / free_area_fracReturn grille sizeOpenA_free = Q / V_face; A_nom = A_free / FA; stock register ≥ A_nomSupply register sizeOpenASP = ESP − ΣΔP_comp; FR = ASP × 100 / TEL (in. w.c./100 ft)Friction rate from ESPOpenL ≥ max(|W1−W2|,|H1−H2|)/2 / tan(θ_wall)Duct transition lengthOpen
Fan
Q₂/Q₁ = N₂/N₁; P₂/P₁ = (N₂/N₁)²; W₂/W₁ = (N₂/N₁)³Fan lawsOpenW = Q ΔP / η (consistent units)Fan BHPOpenQ_net = Q_fan × (1 − derate)Filter derateOpenQ = V_cap × A_openingCapture velocityOpenQ = V_face × A_openPaint booth CFMOpenQ ≈ Q_nom × √(SP_act / SP_nom) (fan-law sketch — not a catalog curve)Fan CFM vs staticOpen
Heat
q_s = 1.08 × CFM × ΔT (IP, std air); SI: q_s ≈ 1.21 × L/s × ΔT_KSensible heatOpenq_l = 0.68 × CFM × ΔW_gr (IP, grains)Latent heatOpenT_m = (Q1 T1 + Q2 T2) / (Q1 + Q2)Mixed-air temperatureOpenCFM = q_s / (1.08 × ΔT)BTU to CFMOpentons = BTU/h / 12,000Cooling tonsOpenCFM = tons × (cfm/ton) (user 350–450)CFM per tonOpentons ≈ A_floor / ft²-per-ton (rule of thumb — not Manual J)AC sizeOpenq ≈ A × U-factor-like × ΔT or BTU/h·ft² × AHeating loadOpenInput = Load / AFUEFurnace sizeOpenCapacity ≥ max(cooling, heating) with user factorsHeat-pump sizeOpenBTU/h ≈ A × BTU/h·ft² (room rule of thumb)Mini-split BTUOpentons = GPM × ΔT / 24 (water, IP)Chiller tonnageOpenq = 1.08 CFM ΔT + 0.68 CFM ΔW_grVentilation loadOpenIntersect load line q = k (T_in − T_out) with capacity lineHeat-pump balance pointOpenq = 1.08 × CFM × (T_supply − T_out) × shareMakeup-air heatingOpenΔT = T_s − T_r; CFM = output / (1.08 × ΔT); output = input × AFUEFurnace temperature riseOpenq = SHGC × A × I × (1 − shade)Window SHGC heat gainOpenW = BTU/h / EER; kWh = W/1000 × hours × duty; COP = EER / 3.412AC running costOpenfree in² each = input / rate; gross = free / free-area; volume = 50 ft³ per 1,000 BTU/hCombustion air openingOpenelectric ft = (BTU/h / 3.412) / (W/ft); hydronic ft = BTU/h / (BTU/h·ft)Baseboard lengthOpenW = area × W/ft² × (1 + 0.125 × feet over 8); BTU/h = W × 3.412; ft = W / 250Baseboard from the roomOpen
Moisture
e_s = 6.112 exp(17.62 t / (243.12 + t)); W = 0.622 e / (P − e)PsychrometricOpenMagnus inverse from e = RH/100 × e_s(t_db)Dew pointOpenIterated from enthalpy / psychrometric identityWet bulbOpenRH = e / e_s(t_db) from DB+DP or DB+WBRelative humidityOpenh ≈ 1.006 t + W (2501 + 1.86 t) kJ/kg, t in °CAir enthalpyOpenW = 0.622 e / (P − e)Humidity ratioOpenpints/day ≈ ρ Q ΔW × 24h (converted)Dehumidifier pintsOpenQ_OA ≈ 0.48 CFM/ft² × A_water (62.1-style talk; sketch)Indoor pool CFMOpensingle ≥ 3/4 in; manifold bands by combined tons; slope 1/8 in/ftCondensate drain sizeOpenGPD = CFM × 60 × 0.075 × Δgrains/7000 × 24 / 8.34Humidifier gallons per dayOpenBF = (T_leave − ADP) / (T_enter − ADP); CF = 1 − BFCoil bypass factorOpen
Water
q = 500 × GPM × ΔT (water, IP)GPM to BTUOpenGPM = BTU/h / (k × ΔT); water k = 500, 30% PG ≈ 480, 50% PG ≈ 450Glycol flowOpenv = 0.4085 GPM / ID²; pick Type L copper at ≤ 4 fpsHydronic pipe sizeOpenH ≈ lift + Σ friction + fittings (user)Pump headOpengal = L × gal/ft + emitters + boiler; glycol = gal × % / 100System volumeOpenV_e ≈ V_sys × e; V_t ≈ V_e / (1 − P1/P2)Expansion tankOpenInput = Load / ηBoiler sizeOpenratio = (Tdesign − Tmild) / (OAoff − OAdesign); T = Tmild + ratio × (OAoff − OAnow)Outdoor resetOpenMakeup ≈ evaporation + blowdown + driftCooling-tower makeupOpenhf/100 ft = 0.2083 (100/C)^1.852 Q^1.852 / d^4.8655Pipe friction (Hazen–Williams)OpenV_gal = t_min × (Q_min − Q_load) / (500 × ΔT)Buffer tank volumeOpenBTU = gal × 8.34 × ΔT; output = BTU / hours; input = output / ηPool heaterOpenBTU = gal × 8.33 × ΔT; BTU/h = BTU / hours × climate × exposure × cover; gas input = BTU/h / ηPool heat lossOpenL = A × 12 / spacing; loops = ceil(L / (L_max − 2 leaders))Radiant floor loopsOpenBTU/h = area × BTU/h·ft²; tube = area × 12 / spacing; loops = ceil(tube / 250)Snow meltOpen