Psychrometric calculators
Magnus dew point, enthalpy, humidity ratio, dehumidifier pints.
Magnus dew point, enthalpy, humidity ratio, dehumidifier pints.
These tools find dew point, wet bulb, relative humidity, enthalpy, humidity ratio, dehumidifier pints and an indoor-pool evaporation sketch from psychrometric states.
They are not a full psychrometric chart engine and not a mold inspection. Magnus saturation pressure is an approximation; barometric pressure matters at altitude.
Open dew-point or RH when you have dry bulb plus one moisture measure. Open enthalpy for coil energy. Open dehumidifier for pints/day from CFM and ΔW. Open indoor-pool for a water-surface sketch.
Enter consistent units (°F/°C, grains or g/kg). Example states on each page match that tool.
Magnus-type es(T). RH = pw / es. Dew point from inverted saturation. Humidity ratio W ≈ 0.622 pw / (P − pw). Enthalpy h ≈ 0.24 t + W(1061 + 0.444 t) in IP.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Use this group when the unknown is a moist-air state or a moisture removal rate. Use heat tools when you already have ΔT or ΔW and want BTU/h.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
70 °F dry bulb at 50% RH is near 50 °F dew point on a sea-level sketch.
Dropping 30 grains across 200 CFM is a dehumidifier pint rate on that page — not a whole-house 62.2 flow.
Two independent measures define the state. RH plus dry bulb also works.
Open air-density if total pressure is not 14.7 psi. Dew-point tools assume a stated P.
Mix humidity ratios and enthalpies, then open mixed-air for dry bulb if needed.
It is an evaporation sketch, not ASHRAE Applications photocopy.
Unit chips convert. The ratio W is the same moisture.
It gives states. Sensible/latent BTU/h is in the heat group.
Moist-air approximations. Instruments, barometer and the project psych chart prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size combustion air, refrigerant charge, fire dampers, medical gas, or electrical conductors.