Combustion Air Opening Calculator

Free combustion-air opening calculator. Free area per opening = appliance input ÷ the rate you pick (4,000, 2,000 or 3,000 BTU/h per in²). Gross opening divides by louver free area. Runs in your browser; not a permit.

Updates in this browser · not a mechanical permit


Formula

Identity
free in² each = input / rate; gross = free / free-area; volume = 50 ft³ per 1,000 BTU/h; mechanical = 0.35 CFM per 1,000
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

Ranking combustion-air calculators size each opening from total appliance input. Two openings straight outdoors or through vertical ducts use 1 in² per 4,000 BTU/h on each opening. Horizontal ducts use 1 in² per 2,000. A single opening uses 1 in² per 3,000. They also show the room volume those pages use for an unconfined space, 50 ft³ per 1,000 BTU/h, and a mechanical supply of 0.35 CFM per 1,000 BTU/h. Metal louvers are preloaded near 75% free, wood near 25%.

Not a flue size and not a substitute for the appliance listing. Sealed combustion that takes its air from outdoors is outside this opening sketch.

Makeup air on this site is for kitchen and dryer exhaust. This page is the air a fuel-burning appliance needs in the mechanical room.

Related calculators on this site:

How to use it

Type total input BTU/h. Chips set 4,000, 2,000 or 3,000 BTU/h per in², and 100%, 75% or 25% free area. Example is 150,000 BTU/h, 4,000, metal at 75%.

Input BTU/h, BTU/h per in², louver free area %.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

free in² each = input / rate; gross = free / free-area; volume = 50 ft³ per 1,000 BTU/h; mechanical = 0.35 CFM per 1,000

Input, the rate and the free-area percent must be positive. Two openings want one high and one low. The adopted rule and the listing still govern.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) 150,000 BTU/h, two direct openings, metal louver.

2) The same room with horizontal ducts at 2,000.

3) A bare opening at 100% free area.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

The Example button uses this set:

150,000 / 4,000 = 37.5 in² free on each opening

37.5 / 0.75 = 50 in² gross. Unconfined volume 7,500 ft³. Mechanical supply 52.5 CFM.

FAQ

4,000 or 2,000?

Direct opening or vertical duct: 1 in² per 4,000 BTU/h on each of two openings. Horizontal duct: per 2,000. One opening: per 3,000. Those are the rates the ranking calculators preload.

Why 150,000 BTU/h?

150,000 / 4,000 = 37.5 in² free on each opening. A metal louver at 75% free makes the cut 50 in².

Input or output?

Input. Output is what is left after efficiency, and it is smaller.

What is 7,500 ft³?

50 ft³ per 1,000 BTU/h, the unconfined-volume check those pages show. 150,000 BTU/h wants 7,500 ft³ or outdoor air.

75% or 25%?

Metal louver about 75% free, wood about 25%, bare opening 100%. Use the grille’s published free area when you have it.

Sealed combustion?

An appliance that takes combustion air from outdoors is outside this opening sketch. Two openings still want one high and one low.

References

Composite of ranking combustion-air calculators. 150,000 BTU/h at 1 in² per 4,000 is their 37.5 in² example, about 50 in² gross behind a 75% metal louver. Input, not output.

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.

Disclaimer

Estimate only, using the rates the ranking calculators preload. The listing, the adopted fuel-gas rule and the grille’s published free area prevail.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.