Fan laws, BHP and capture calculators
Affinity laws, filter derate, paint-booth and hood capture.
Affinity laws, filter derate, paint-booth and hood capture.
These tools apply fan affinity laws, estimate BHP from CFM and static pressure, derate a dirty filter, and sketch capture velocity, paint-booth face flow and actual delivered CFM.
They are not a fan curve from the manufacturer and not a listed spray-booth certificate. Use the nameplate RPM, SP and efficiency the OEM published.
Open fan laws when RPM, CFM or SP change together. Open fan-BHP for air horsepower × efficiency. Open filter-derate when the filter loads. Open capture or paint-booth for face velocity × area.
You need a baseline CFM and pressure from a duct or hood page, then a new RPM or a new SP.
Q₂/Q₁ = N₂/N₁; SP₂/SP₁ = (N₂/N₁)²; BHP₂/BHP₁ = (N₂/N₁)³. Air power ≈ CFM × SP / 6356. Capture Q ≈ V_face × A.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Use this group after you have a system CFM. Use duct tools for the pressure that feeds BHP.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
A fan at 1000 CFM, 0.5 in. w.g., 60% total efficiency is about 0.13 BHP before motor losses.
Raise RPM 10% and the laws say about 10% more CFM, 21% more SP, 33% more BHP — until the system curve disagrees.
No. They scale one operating point. Stall, density and system effect stay on the OEM sheet.
A dirty filter raises SP and cuts delivered CFM. The page is a sketch, not a MERV table.
Face velocity × open area. Confirm the booth listing.
Capture velocity is at the opening. Kitchen-hood has its own rules of thumb.
Fan-actual compares nameplate flow at a test SP with a field static.
BHP is mechanical. Wire and breaker pages are not on this host.
Affinity laws assume the same fan and a system that still sits on a similar curve.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size combustion air, refrigerant charge, fire dampers, medical gas, or electrical conductors.