A US cooling ton is 12,000 BTU/h. Conventional air-handler talk moves about 400 CFM of supply air per ton, so a 3-ton unit is often 1,200 CFM at the blower table. Lower CFM/ton (around 350) leaves air on the coil longer and can help dehumidify in humid climates if the coil and TXV actually behave. Higher CFM/ton (450) is more mixing, less latent, common in dry climates. The identity is CFM = tons × (CFM/ton).
This is not how you size the AC. Floor-area rules (500 ft²/ton and friends) live on AC size and are explicitly not Manual J. CFM/ton only splits airflow after capacity exists. A 3-ton machine at 400 CFM/ton is 1,200 CFM whether the house needed 2 tons or 4.
What to open
CFM per ton with chips 350 / 400 / 450. Cooling tons converts BTU/h. Sensible heat checks whether that CFM can carry the sensible load at a reasonable ΔT (often 15–20 °F on the air side).
Worked numbers
36,000 BTU/h = 3 tons × 400 = 1,200 CFM. At 1.08 and 20 °F rise, sensible capacity ≈ 25,900 BTU/h, the rest is latent budget — not a promise.
FAQ
Two-stage and variable speed?
They change CFM with load. 400 CFM/ton is a full-capacity talk, not every tap.
Ductless?
Indoor heads are rated in CFM at a fan speed, not always 400 CFM/ton. Use the OEM table.
Heat pumps in heat mode?
Airflow may differ from cooling. Read the installation manual.
Can I raise CFM to fix a hot room?
You may lose latent control and noise the ducts. Find the load and the balancing damper first.
Chilled water?
GPM/ton is a water-side cousin (often 2.4 GPM/ton at 10 °F). Open chiller-tonnage.
Limits
Not a blower-table reprint and not a humidity-control guarantee.
Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.