Free Fan laws Calculator. affinity-law scaling of CFM, pressure and power when you change speed or wheel diameter. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts affinity-law scaling of CFM, pressure and power when you change speed or wheel diameter. It is the Fan laws tool in the fan group on ACH Calculator.
It is not a manufacturer catalog interpolation or a VFD harmonics study. If you need those, open a related tool instead of stretching this identity.
The identity on screen is Q∝N; P∝N²; W∝N³ (same fan, same system curve, density constant). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: Known Q1,P1,W1,N1; new N2 or D2; density ratio optional. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
Q∝N;
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) Balancing a pulley from 1000 to 900 rpm.
2) VFD 80% speed power.
3) Wheel diameter change — rare in field.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
N2/N1=0.9
Q2=0.9 Q1
P2=0.81 P1
W2=0.729 W1
Work the same arithmetic on paper; the live result should match within rounding.
When you leave the system curve, stall, or change density a lot without the density form. Inlet vanes are not a pure speed change.
Q∝D³, P∝D², W∝D⁵ at constant N — shop talk, not a field pulley.
Pressure and power scale with ρ at constant Q and N.
1 hp = 0.746 kW. Open fan-bhp for the definition of W from Q ΔP.
Parallel/series laws are different. This is one fan.
Not a fan law on this page.
Primary identity: Q∝N; P∝N²; W∝N³ (same fan, same system curve, density constant). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.
Estimate only for Fan laws. Adopted mechanical codes, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.