Free Duct offset Calculator. the centerline length and run of a duct offset given rise and fitting angle — HVAC geometry, not electrical conduit. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts the centerline length and run of a duct offset given rise and fitting angle — HVAC geometry, not electrical conduit. It is the Duct offset tool in the duct group on ACH Calculator.
It is not a conduit-bender multiplier table or an HVAC fitting C. If you need those, open a related tool instead of stretching this identity.
The identity on screen is L_center = offset / sin θ; run = offset / tan θ. Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: Offset distance, angle 15/22.5/30/45/60, result throat/centerline. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
L_center = offset / sin θ;
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 8 in offset at 45°.
2) 15° long-radius to keep C down.
3) Matching two elbows.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
offset = 8 in
θ = 45°
L = 8 / sin 45° ≈ 11.3 in
Work the same arithmetic on paper; the live result should match within rounding.
Same trigonometry, different fittings. Do not use electrician multipliers as HVAC C values.
Two 45s plus a straight is an offset. Loss is two fittings plus the straight.
Geometry still holds; C is worse than a stamped elbow.
Run along the original axis is offset / tan θ.
This is planar. A rolled offset is two planes — sketch twice.
Flex can snake without a defined θ; friction rises. Prefer fittings.
Primary identity: L_center = offset / sin θ; run = offset / tan θ. Interpret it with the sources listed below, not as a photocopy of a copyrighted table.
Estimate only for Duct offset. Adopted mechanical codes, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.