Free Makeup-air heating calculator. Winter MAU output q = 1.08 × CFM × (T_supply − T_outdoor) × share. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
Ranking makeup-heater calculators all use the sensible identity with outdoor design temperature and a supply setpoint (often 65 °F so the kitchen stays within about 10 °F of the room). Share lets the unit cover 80–100% of exhaust. Input = output / efficiency. 3,000 CFM from 0 °F to 65 °F = 210,600 BTU/h is the worked example they repeat.
It is not summer cooling/dehumidification of makeup air and not a burner selection curve.
Sensible-heat is the same 1.08 with a room ΔT. This page names outdoor and supply so a kitchen MAU is not confused with a furnace rise.
Related calculators on this site:
Type exhaust CFM (or 80% of it), outdoor design T, supply T. Example is 3,000 CFM, 0 °F to 65 °F, 80% efficient.
CFM, T_out, T_supply, share %, efficiency %.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
q = 1.08 × CFM × (T_supply − T_out) × share;
Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 3,000 CFM kitchen MAU, 0 °F to 65 °F.
2) 80% share, transfer air for the rest.
3) Direct-fired vs 80% indirect input.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
3,000 CFM, 0 → 65 °F, 100% share
q = 1.08 × 3000 × 65 = 210,600 BTU/h
80% → input 263,250 BTU/h
IMC-family talk about keeping supply within about 10 °F of the room so staff are not blasted with 0 °F air.
Standard-air factor. Cold air is denser; OEM heaters correct for it. This page stays on 1.08.
Keeps the kitchen slightly negative. Heat only the CFM the unit actually handles.
A different coil. Do not use this winter identity in August.
Input BTU/h ÷ 1,000 if the gas is 1,000 BTU/ft³. Check the bill of fuel.
Transfer air or another AHU must make up the rest or the hood starves.
Composite of ranking MAU-heat pages. Elevation/density corrections are omitted; open air-density for Denver.
Estimate only for makeup-air heating. IMC 508, OEM data and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.