Duct size, velocity and pressure calculators
Round/rect size, Huebscher, friction, fittings, SCFM/ACFM.
Round/rect size, Huebscher, friction, fittings, SCFM/ACFM.
These tools size round and rectangular ducts from CFM and velocity or friction, convert Huebscher equivalent diameter, and sketch fitting loss, offset, static pressure, TEL, SCFM/ACFM and return-grille face area.
They are not a SMACNA takeoff, not a noise model, and not a fire-damper schedule. Fire/smoke ducts follow that specification.
Open duct size with CFM and a velocity or friction target. Use equivalent-duct for rectangle ↔ round. Use friction and fittings when you are adding pressure. Use return-grille for face velocity × area.
Bring CFM from the air tools if you have a room or hood. Example numbers on each page match that tool’s worked section.
Q = V × A. Huebscher De = 1.30(ab)^0.625 / (a+b)^0.25. Friction sketches use a Darcy-style rate per 100 ft. Dynamic loss ≈ C × VP.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Use this group when CFM is known and the unknown is diameter, aspect ratio, or pressure. Use fan tools for BHP and laws.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
400 CFM at 700 fpm → area 0.57 ft² → about 10 in round. A 12×8 in rectangle has a Huebscher De near 10.7 in.
A quiet residential friction talk is often 0.08–0.10 in. w.g. per 100 ft — confirm on duct-friction, not from memory.
Velocity is a first diameter. Equal friction is a pressure budget along a run. They are different pages.
It is a published equivalent-diameter relation, not a required size.
Density changes with altitude and temperature. Open scfm-acfm / air-density.
Fitting-loss and offset are extra. A straight-duct friction page is not a full TEL.
Face velocity over about 500 fpm is a common noise complaint. Open return-grille.
Yes, once you have CFM and a static-pressure sketch.
Geometry sketches. Manufacturer fittings, lining and the adopted duct standard prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size combustion air, refrigerant charge, fire dampers, medical gas, or electrical conductors.