Duct size, velocity and pressure calculators

Round/rect size, Huebscher, friction, fittings, SCFM/ACFM.

Duct

Duct sizeRound or rectangular duct size from CFM and a target velocity, or from a user equal-friction rate.Duct velocityMean duct velocity from airflow and cross-section (round diameter or W×H).Equivalent round ductHuebscher equivalent round diameter of a rectangular duct so friction comparisons stay honest.Duct frictionStraight-duct pressure drop from a typed friction rate or a Darcy-Weisbach sketch with user roughness.Fitting lossA fitting pressure drop from a user loss coefficient C and velocity (dynamic pressure).Duct offsetThe centerline length and run of a duct offset given rise and fitting angle — HVAC geometry, not electrical conduit.Static pressureA fan external static budget by adding the pressure drops you type.Total equivalent lengthPressure drop from total equivalent length and a friction rate — the residential TEL method.Duct aspect ratioAspect ratio of a rectangular duct and the equivalent diameter penalty as AR grows at constant area.SCFM to ACFMActual cubic feet per minute from standard CFM using the temperatures and pressures you type.Air densityMoist or dry air density from temperature, pressure or altitude so 1.08 and fan power stay honest.Return grille sizeReturn (or supply) grille size from CFM, face velocity, and a free-area fraction.Supply register sizeStock floor or ceiling register from room CFM, face velocity and free-area share.Friction rate from ESPAvailable static pressure after coil, filter and fittings, then FR = ASP × 100 / TEL.Duct transition lengthMinimum centered reducer length from wall angle: L = max(ΔW, ΔH)/2 / tan(θ).

What this calculator does

These tools size round and rectangular ducts from CFM and velocity or friction, convert Huebscher equivalent diameter, and sketch fitting loss, offset, static pressure, TEL, SCFM/ACFM and return-grille face area.

They are not a SMACNA takeoff, not a noise model, and not a fire-damper schedule. Fire/smoke ducts follow that specification.

How to use it

Open duct size with CFM and a velocity or friction target. Use equivalent-duct for rectangle ↔ round. Use friction and fittings when you are adding pressure. Use return-grille for face velocity × area.

Bring CFM from the air tools if you have a room or hood. Example numbers on each page match that tool’s worked section.

Formula, units, and limits

Q = V × A. Huebscher De = 1.30(ab)^0.625 / (a+b)^0.25. Friction sketches use a Darcy-style rate per 100 ft. Dynamic loss ≈ C × VP.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Use this group when CFM is known and the unknown is diameter, aspect ratio, or pressure. Use fan tools for BHP and laws.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

400 CFM at 700 fpm → area 0.57 ft² → about 10 in round. A 12×8 in rectangle has a Huebscher De near 10.7 in.

A quiet residential friction talk is often 0.08–0.10 in. w.g. per 100 ft — confirm on duct-friction, not from memory.

FAQ

Velocity or equal friction?

Velocity is a first diameter. Equal friction is a pressure budget along a run. They are different pages.

Is Huebscher a code?

It is a published equivalent-diameter relation, not a required size.

SCFM versus ACFM?

Density changes with altitude and temperature. Open scfm-acfm / air-density.

Does this include fittings?

Fitting-loss and offset are extra. A straight-duct friction page is not a full TEL.

Return grille too loud?

Face velocity over about 500 fpm is a common noise complaint. Open return-grille.

Can I skip to a fan?

Yes, once you have CFM and a static-pressure sketch.

References

Disclaimer

Geometry sketches. Manufacturer fittings, lining and the adopted duct standard prevail.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size combustion air, refrigerant charge, fire dampers, medical gas, or electrical conductors.