Glycol Flow Calculator

Free glycol flow calculator. GPM = BTU/h / (factor × ΔT). Water uses 500. About 30 percent propylene glycol uses 480, and about 50 percent uses 450.

Updates in this browser · not a mechanical permit


Formula

Identity
GPM = BTU/h / (factor × ΔT)
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

This page turns a hydronic load into flow when the loop is not plain water. GPM = BTU/h / (factor × ΔT). Water uses 500, from 8.33 pounds per gallon and 60 minutes. About 30 percent propylene glycol uses 480. About 50 percent uses 450. Glycol carries less heat per gallon, so the same load needs more flow.

Not a freeze-point chart, and not the gallons of antifreeze to buy. The other GPM page on this site stays on water at 500.

Leave the factor at 500 for water. 480 and 450 are the two glycol steps.

Related calculators on this site:

How to use it

Type BTU/h, the design ΔT, and the fluid factor. Chips are 500, 480, and 450. The example is 60,000 BTU/h, 20°F, water.

BTU/h, ΔT °F, fluid factor.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

GPM = BTU/h / (factor × ΔT)

Load, ΔT, and the factor must be positive. 480 and 450 are the round factors for about 30 percent and about 50 percent propylene glycol, not a full fluid table.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) 60,000 BTU/h, 20°F, water at 500.

2) The same load at 480.

3) The same load at 450.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

The example is 60,000 BTU/h at a 20°F rise on water:

60,000 / (500 × 20) = 6.00 GPM

The same load at 480 is 6.25 GPM. At 450 it is 6.67 GPM.

FAQ

Why 500?

It is 8.33 pounds per gallon, one BTU per pound per degree, and 60 minutes. 8.33 × 60 is about 500.

Why 480 and 450?

Those are the round factors for about 30 percent and about 50 percent propylene glycol. Glycol holds less heat per gallon than water.

How much extra flow?

60,000 BTU/h at 20°F is 6.00 GPM on water, 6.25 GPM at 480, and 6.67 GPM at 450.

Is 1 GPM per 10,000 BTU/h always right?

Only for water at a 20°F rise, because 500 × 20 = 10,000. A different rise or glycol changes it.

Where is the pipe size?

On the hydronic pipe page. This page stops at GPM.

Same as the other GPM page?

That page is water at 500, and it can also solve for BTU/h or ΔT. This page is the glycol factor.

References

Water is 500. About 30 percent propylene glycol is 480, about 4 percent more flow. About 50 percent is 450, about 11 percent more flow. One GPM per 10,000 BTU/h is the water case at 20°F.

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.

Disclaimer

Estimate only. Use the fluid maker’s specific heat when the mix is not one of these three.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.