Sensible heat Calculator

Free Sensible heat Calculator. sensible heating or cooling rate of an airstream from CFM and dry-bulb difference. Runs in your browser; not a permit or a Manual J.

Updates in this browser · not a mechanical permit


Formula

Identity
q_s = 1.08 × CFM × ΔT (IP std air); q_s ≈ 1.21 × L/s × ΔT_K (SI)
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

This page converts sensible heating or cooling rate of an airstream from CFM and dry-bulb difference. It is the Sensible heat tool in the heat group on ACH Calculator.

It is not latent load, a Manual J envelope load, or a psychrometric coil process with bypass factor. If you need those, open a related tool instead of stretching this identity.

The identity on screen is q_s = 1.08 × CFM × ΔT (IP std air); q_s ≈ 1.21 × L/s × ΔT_K (SI). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.

Related calculators on this site:

How to use it

Use the fields that match the job: CFM (or L/s), T_in, T_out, density/1.08 override. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

q_s = 1.08 × CFM × ΔT (IP std air); q_s ≈ 1.21 × L/s × ΔT_K (SI)

Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) Supply 400 CFM, 20 °F ΔT.

2) OA ventilation load.

3) Reheat coil.

If the job is life-safety, sterile, or listed equipment, stop here and use the specification.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

The Example button uses this set:

CFM=400

ΔT=20 °F

q_s = 1.08×400×20 = 8640 BTU/h

Work the same arithmetic on paper; the live result should match within rounding.

FAQ

Where is 1.08 from?

≈ 0.24 BTU/lb·°F × 0.075 lb/ft³ × 60 min/h. At altitude or odd humidity, scale with density.

SI 1.21?

≈ 1.006 kJ/kg·K × 1.2 kg/m³. L/s × K gives watts when using 1.21.

Enter two temperatures?

ΔT is |T_leave − T_enter|. Sign shows heat vs cool if you care.

Latent?

Open latent-heat. Total coil is sensible + latent.

400 CFM/ton?

That rule implies about 30 °F ΔT on 12,000 BTU/h: 1.08×400×27.8 ≈ 12,000. Open cfm-per-ton.

Mixed air?

Get T_mix first on mixed-air, then ΔT to supply.

References

Primary identity: q_s = 1.08 × CFM × ΔT (IP std air); q_s ≈ 1.21 × L/s × ΔT_K (SI). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.

Disclaimer

Estimate only for Sensible heat. Adopted mechanical codes, OEM curves and a licensed designer prevail.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.