Free outdoor reset calculator. Reset ratio = supply span / outdoor span. Supply at any outdoor temperature sits on that straight line.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page turns the two ends of a boiler curve into a reset ratio and the supply temperature at the outdoor temperature you type. The line runs from the design outdoor temperature and its supply to the warm-weather shutdown and its supply. The result stays between those two supply temperatures.
Not a heat-loss calculation, and not a mixing-valve size. The boiler still needs its own return-water limit.
The example is 180°F supply at 0°F outdoor and 80°F supply at 70°F outdoor. Radiators and fin-tube often use a steeper curve, about 1.4 to 1.8. Radiant floors often use a flatter one, about 0.6 to 1.0.
Related calculators on this site:
Type the design outdoor temperature, the supply there, the shutdown outdoor temperature, the supply there, and the outdoor temperature to check. The example checks 30°F.
Design outdoor °F, design supply °F, shutdown outdoor °F, mild supply °F, outdoor now °F.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
ratio = (design supply − mild supply) / (shutdown outdoor − design outdoor);
The two outdoor temperatures must differ. Supply is held between the two supply temperatures you entered.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 180°F at 0°F outdoor, 80°F at 70°F outdoor, checked at 30°F.
2) The same supply ends with shutdown at 65°F outdoor.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The supply span is 180 − 80 = 100°F. The outdoor span is 70 − 0 = 70°F. The ratio is 100 / 70 = 1.43. At 30°F the supply is 137°F.
The same supply ends with shutdown at 65°F give a ratio of 1.54 and about 134°F at 30°F.
(180 − 80) / (70 − 0) = 100 / 70 = 1.43.
At 30°F the line from 180°F at 0°F to 80°F at 70°F lands on 137°F.
(180 − 80) / (65 − 0) = 1.54. At 30°F the supply is about 134°F.
Fin-tube and cast iron are often 1.4 to 1.8. Radiant floors are often 0.6 to 1.0, with a lower design supply.
On a condensing boiler it is what keeps return water under about 130°F for much of the season. Above that the boiler stops condensing.
The warm end of the curve is low. Raise the supply at shutdown a few degrees, and leave the design end until the coldest days are wrong.
The curve is a straight line between the design point and the warm-weather point. A condensing boiler condenses when return water is below about 130°F.
Estimate only. A non-condensing boiler still needs its return kept hot enough. Follow the control maker’s settings.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.