公式
ツールと同じ式。
空気
CFM = ACH × Volume / 60換気回数とCFM開くrequired = max(50 CFM code floor, HVI area or fixtures, 8 ACH); buy next common fan浴室換気扇開くQ = max(100 CFM, 100 or 150 CFM/ft × width, BTU/h ÷ 100); flag makeup air if Q > 400レンジフード開くQ_vent = 0.03 A_floor + 7.5 (N_br + 1) (ASHRAE 62.2 form, IP)ASHRAE 62.2開くV_bz = Rp × Pz + Ra × Az (ASHRAE 62.1 breathing-zone form)ASHRAE 62.1 外気開くif Q_exh > 400 CFM then Q_mu ≈ Q_exh, else 0 (IRC talk; not Q_exh − 400)給気補償開くCFM = ACH × V / 60 or CFM = cfm/ft² × A車庫排気開くA_net ≈ A_attic / 150 (or /300); split 50/50 intake/exhaust NFA in in²小屋裏換気開くCFM = ACH_ISO × V / 60 (ACH from user ISO class pick or custom)クリーンルーム換気回数開くQ = V × exchanges/min × (1 + filter%) × lights (1/min is the common tent sketch)グロウテント風量開くACH = CADR × 60 / V; also CADR_5ACH = V × 5 / 60CADR換気回数開くACH_nat ≈ ACH50 / N; CFM_nat ≈ CFM50 / N (N chips 20/16/13)ACH50と自然換気開くCFM = ACH × V / 60 or CFM = cfm/ft² × A駐車場換気開くQ_sys = tons × CFM/ton; Q_room = Q_sys × (A×f) / Σ(A×f)部屋別CFM開くQ = n × CFM/unit or Q = A × CFM/ft² (user-typed rates)業務用排気開くQ = L_hood × CFM/ft (wall canopy 200/300/400/550 by duty)業務用フード開くQ_tot = dryer + hood + baths; makeup if hood>400 or dryer>200乾燥機排気開くCFM = A × (CFM/ft²) × (H/8); NFA = CFM/750; window = CFM/750全館ファン開くCFM = (A × H) / minutes; 2 min = 30 ACH, 3 min = 20 ACH気化式冷風機開くCFM = attic floor × 0.7 (dark or steep × 0.805); intake = CFM / 300小屋裏ファン開くQ/person = G / ((C_in − C_out)/10^6)CO₂ から風量開くQ = 0.03 A + 7.5 (N_br + 1); q_recovered = 1.08 × Q × ΔT × εERV/HRV の回収熱開く
ダクト
equal-friction d = (0.109136 × Q^1.9 / f)^(1/5.02); also A = Q/Vダクトサイズ開くV = Q / Aダクト風速開くDe = 1.30 (a b)^0.625 / (a + b)^0.25 (Huebscher)相当円形ダクト開くΔP/L from user friction rate × length, or Darcy-Weisbach sketchダクト摩擦開くΔP = C × (ρ/2) V²継手損失開くL_center = offset / sin θ; heel-throat from geometryダクトオフセット開くESP ≈ Σ ΔP_duct + Σ ΔP_fit + ΔP_coil/filter (user terms)静圧開くΔP = f × TEL相当長さ開くAR = a/b; area held, De from Huebscherアスペクト比開くACFM = SCFM × (T_act/T_std) × (P_std/P_act)SCFMとACFM開くρ = P / (R T) dry-air sketch; altitude optional空気密度開くA_free = Q / V_face; A_nominal = A_free / free_area_frac還気グリル開くA_free = Q / V_face; A_nom = A_free / FA; stock register ≥ A_nom給気レジスター開くASP = ESP − ΣΔP_comp; FR = ASP × 100 / TEL (in. w.c./100 ft)ESPから摩擦率開くL ≥ max(|W1−W2|,|H1−H2|)/2 / tan(θ_wall)ダクト径違い長さ開く
ファン
熱
q_s = 1.08 × CFM × ΔT (IP, std air); SI: q_s ≈ 1.21 × L/s × ΔT_K顕熱開くq_l = 0.68 × CFM × ΔW_gr (IP, grains)潜熱開くT_m = (Q1 T1 + Q2 T2) / (Q1 + Q2)混合温度開くCFM = q_s / (1.08 × ΔT)BTUとCFM開くtons = BTU/h / 12,000冷凍トン開くCFM = tons × (cfm/ton) (user 350–450)トンあたりCFM開くtons ≈ A_floor / ft²-per-ton (rule of thumb — not Manual J)エアコン能力目安開くq ≈ A × U-factor-like × ΔT or BTU/h·ft² × A暖房負荷目安開くInput = Load / AFUE炉容量開くCapacity ≥ max(cooling, heating) with user factorsヒートポンプ容量開くBTU/h ≈ A × BTU/h·ft² (room rule of thumb)壁掛けBTU開くtons = GPM × ΔT / 24 (water, IP)チラー能力開くq = 1.08 CFM ΔT + 0.68 CFM ΔW_gr外気負荷開くIntersect load line q = k (T_in − T_out) with capacity lineHPバランスポイント開くq = 1.08 × CFM × (T_supply − T_out) × share外気加熱開くΔT = T_s − T_r; CFM = output / (1.08 × ΔT); output = input × AFUE炉温度上昇開くq = SHGC × A × I × (1 − shade)窓SHGC開くW = BTU/h / EER; kWh = W/1000 × hours × duty; COP = EER / 3.412冷房の運転費開くfree in² each = input / rate; gross = free / free-area; volume = 50 ft³ per 1,000 BTU/h燃焼空気の開口開くelectric ft = (BTU/h / 3.412) / (W/ft); hydronic ft = BTU/h / (BTU/h·ft)ベースボードの長さ開くW = area × W/ft² × (1 + 0.125 × feet over 8); BTU/h = W × 3.412; ft = W / 250部屋からベースボード開く
湿り
e_s = 6.112 exp(17.62 t / (243.12 + t)); W = 0.622 e / (P − e)湿り空気開くMagnus inverse from e = RH/100 × e_s(t_db)露点開くIterated from enthalpy / psychrometric identity湿球開くRH = e / e_s(t_db) from DB+DP or DB+WB相対湿度開くh ≈ 1.006 t + W (2501 + 1.86 t) kJ/kg, t in °Cエンタルピー開くW = 0.622 e / (P − e)絶対湿度比開くpints/day ≈ ρ Q ΔW × 24h (converted)除湿パイント開くQ_OA ≈ 0.48 CFM/ft² × A_water (62.1-style talk; sketch)室内プール換気開くsingle ≥ 3/4 in; manifold bands by combined tons; slope 1/8 in/ftドレン管径開くGPD = CFM × 60 × 0.075 × Δgrains/7000 × 24 / 8.34加湿器 gal/日開くBF = (T_leave − ADP) / (T_enter − ADP); CF = 1 − BFバイパス係数開く
水
q = 500 × GPM × ΔT (water, IP)GPMとBTU開くGPM = BTU/h / (k × ΔT); water k = 500, 30% PG ≈ 480, 50% PG ≈ 450グリコール流量開くv = 0.4085 GPM / ID²; pick Type L copper at ≤ 4 fps配管径開くH ≈ lift + Σ friction + fittings (user)ポンプ揚程開くgal = L × gal/ft + emitters + boiler; glycol = gal × % / 100系統容量開くV_e ≈ V_sys × e; V_t ≈ V_e / (1 − P1/P2)膨張タンク開くInput = Load / ηボイラー容量開くratio = (Tdesign − Tmild) / (OAoff − OAdesign); T = Tmild + ratio × (OAoff − OAnow)外気リセット開くMakeup ≈ evaporation + blowdown + drift冷却塔補給水開くhf/100 ft = 0.2083 (100/C)^1.852 Q^1.852 / d^4.8655配管摩擦開くV_gal = t_min × (Q_min − Q_load) / (500 × ΔT)バッファタンク開くBTU = gal × 8.34 × ΔT; output = BTU / hours; input = output / ηプール加熱器開くBTU = gal × 8.33 × ΔT; BTU/h = BTU / hours × climate × exposure × cover; gas input = BTU/h / ηプール熱損失開くL = A × 12 / spacing; loops = ceil(L / (L_max − 2 leaders))床暖房のループ開くBTU/h = area × BTU/h·ft²; tube = area × 12 / spacing; loops = ceil(tube / 250)融雪負荷開く