Free snow-melt calculator. BTU/h = area × BTU/h per ft². Tube length = area × 12 / spacing. Loops divide that length by about 250 ft.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page sizes a heated driveway or walk from the heat per square foot you type. Snow melt runs about 80 to 230 BTU/h per ft². Indoor heat is about 20 to 40. The worked case is 150 BTU/h per ft². Tube length is area × 12 / the spacing in inches. Loops stay near 250 ft because the flow is high.
Not an indoor radiant room, and not a class-and-climate chart. Type the BTU/h per ft². The outdoor loop also needs glycol and insulation under the slab.
150 is the worked case. 80 and 230 are the ends of the stated band. Spacing chips are 6, 9, and 12 inches.
Related calculators on this site:
Type area, BTU/h per ft², spacing, and the loop limit. The example is 600 ft² at 150, 9 inch spacing, 250 ft loops.
Area ft², BTU/h per ft², spacing inches, max loop ft.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
BTU/h = area × BTU/h·ft²;
Area, the flux, spacing, and the loop limit must be positive. This does not pick a class or a climate for you.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 600 ft² at 150 BTU/h per ft², 9 inch spacing.
2) The same slab at 80 or 230.
3) The same slab at 6 or 12 inch spacing.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The example is a 600 ft² slab at 150 BTU/h per ft² and 9 inch spacing:
600 × 150 = 90,000 BTU/h
600 × 12 / 9 = 800 ft, in 4 loops of about 250 ft. That load is paired with about a 100,000 BTU/h boiler.
That is the worked cell: a cold, mostly clear surface. 600 ft² × 150 = 90,000 BTU/h.
The low and high ends of the snow-melt band on that sizing note. Indoor heating on the same note is 20 to 40.
Tube length is area × 12 / spacing. 600 × 12 / 9 = 800 ft. Dividing by about 250 ft gives 4 loops.
The 90,000 BTU/h load in the worked case is paired with about a 100,000 BTU/h boiler. This page does not apply a hidden multiplier.
Yes. The outdoor loop sits cold for most of the year. Use the glycol flow page for the GPM once the mix is chosen.
No. The indoor page is tube in a room, with a 300 ft planning cap and leaders. This page is the outdoor slab, with shorter loops.
The stated band is 80 to 230 BTU/h per ft². The worked cell is 150. Indoor heat on the same note is 20 to 40. Loops are kept near 250 ft.
Estimate only. The slab, the insulation under it, and the glycol mix control the real boiler.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.