Free Cooling-tower makeup Calculator. cooling-tower makeup water from a circulating GPM, range ΔT, cycles of concentration, and drift you type. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts cooling-tower makeup water from a circulating GPM, range ΔT, cycles of concentration, and drift you type. It is the Cooling-tower makeup tool in the water group on ACH Calculator.
It is not a water-treatment chemical dose, a Legionella program, or a tower selection catalog. If you need those, open a related tool instead of stretching this identity.
The identity on screen is Makeup ≈ evaporation + blowdown + drift; E ≈ 0.001 × GPM × ΔT_F (rule of thumb, US gpm). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: GPM, range ΔT, cycles N, drift %, result E, B, D, makeup. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
Makeup ≈ evaporation + blowdown + drift;
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 1000 GPM, 10 °F range, 3 cycles.
2) Zero-drift claim as 0.0005%.
3) Winter basin heat — not modeled.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
E ≈ 0.001×1000×10 = 10 GPM
N=3
B = E/(N−1) = 5 GPM
Work the same arithmetic on paper; the live result should match within rounding.
A US rule of thumb for evaporation. Latent heat of vaporization makes it roughly right, not a metering law.
How much you concentrate dissolved solids. Blowdown B = E/(N−1) for simple mass balance.
Liquid droplets. Modern eliminators are a small % of GPM. Type the vendor number.
Not in the identity.
Different water use. Do not paste this makeup.
GPM still comes from chiller-tonnage / gpm-btu.
Primary identity: Makeup ≈ evaporation + blowdown + drift; E ≈ 0.001 × GPM × ΔT_F (rule of thumb, US gpm). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.
Estimate only for Cooling-tower makeup. Adopted mechanical codes, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.