Free Duct size Calculator. round or rectangular duct size from CFM and a target velocity, or from a user equal-friction rate. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts round or rectangular duct size from CFM and a target velocity, or from a user equal-friction rate. It is the Duct size tool in the duct group on ACH Calculator.
It is not a full ASHRAE fitting database, a CAMEL takeoff, or an SMACNA gauge table. If you need those, open a related tool instead of stretching this identity.
The identity on screen is equal-friction d = (0.109136 × Q^1.9 / f)^(1/5.02), default f = 0.08 in/100 ft, plus optional velocity sizing. Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: CFM, friction rate (default 0.08), optional velocity. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
CFM, friction in/100 ft (default 0.08), optional FPM. Result is round diameter, stock size, Huebscher 8 in rect.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
d = (0.109136 × Q^1.9 / f)^(1/5.02);
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 400 CFM supply at 700 fpm → ~10 in round.
2) Return at 600 fpm.
3) Equal friction 0.08 in/100 ft as a user rate.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
Q = 400 CFM at 0.08 in/100 ft
d ≈ 9.3 in → stock 10 in round
Work the same arithmetic on paper; the live result should match within rounding.
Residential often starts from velocity (or a friction like 0.08–0.10 in/100 ft). Commercial mains may be faster. You type the criterion.
Same area is only a start. Huebscher equivalent diameter is on the equivalent-duct page.
High FPM at registers is a noise complaint. Use the duct-velocity chart.
Flex has higher friction than smooth metal. Use a higher friction rate or a lower velocity.
This sizes one path. Branch takeoffs need split CFM.
Pressure class and metal gauge are construction, not this area calc.
Primary identity: A = Q / V; D = √(4A/π); equal-friction optional from user f. Interpret it with the sources listed below, not as a photocopy of a copyrighted table.
Estimate only for Duct size. Adopted mechanical codes, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.