This page converts actual cubic feet per minute from standard CFM using the temperatures and pressures you type. It is the SCFM to ACFM tool in the duct group on ACH Calculator.
It is not a moisture-saturated compressor table or a mass-flow Coriolis reading. If you need those, open a related tool instead of stretching this identity.
The identity on screen is ACFM = SCFM × (T_act/T_std) × (P_std/P_act). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: SCFM, T_act, T_std (70 °F / 20 °C chips), P_act, P_std. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
ACFM = SCFM × (T_act/T_std) × (P_std/P_act)
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) Hot attic air vs 70 °F standard.
2) High-altitude job.
3) Fan catalog SCFM vs site ACFM.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
SCFM=1000
T_act=100 °F = 560 R
T_std=530 R
P same
ACFM ≈ 1057
Work the same arithmetic on paper; the live result should match within rounding.
US HVAC often 70 °F and 14.696 psi or 29.92 in Hg, dry. Compressors may use 14.7 psi, 68 °F, 36% RH. Type the standard you were given.
Rankine or Kelvin. 70 °F = 530 R; 21 °C ≈ 294 K.
Wet air is lighter. This page is the dry ideal-gas sketch unless you also use psychrometric.
lb/h = ACFM × ρ. Density from air-density.
Fans move ACFM; mass and power follow density.
29.92 inHg ≈ 14.696 psi. Use absolute pressure, not gauge.
Primary identity: ACFM = SCFM × (T_act/T_std) × (P_std/P_act). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.