Free Duct transition length calculator. Minimum centered reducer length from wall angle: L = max(ΔW, ΔH)/2 / tan(θ). Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
Ranking transition calculators agree on the geometry: a centered reducer splits the width and height change across two walls; L_min = max(|W1−W2|,|H1−H2|)/2 / tan(θ) with θ the wall-to-axis angle. 15° is the default they share; 7.5° is the gentler expansion; 30° is short and lossy. Optional CFM reports inlet and outlet velocity. Loss coefficients stay on fitting-loss.
It is not an ASHRAE fitting-loss table (SR4-2) and not a square-to-round pattern development.
Duct-offset solves a jog. This page only stretches or shrinks the cross-section on one centerline.
Related calculators on this site:
Type both openings in inches and leave 15°. Example is 16×8 to 12×8. Add CFM if you want V1 and V2.
W1, H1, W2, H2, wall angle chips 7.5/15/30, optional CFM.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
L ≥ max(|W1−W2|,|H1−H2|)/2 / tan(θ_wall)
Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 16×8 trunk to 12×8 after a takeoff.
2) Round-to-rect treated as W×H vs D×D.
3) Check a 30° shop fitting against 15° spec.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
16×8 → 12×8, θ=15°
ΔW/2=2 in; ΔH/2=0
L = 2 / tan 15° ≈ 7.5 in
This page uses the wall-to-axis angle ranking geometry tools use. A symmetric 15° wall is a 30° included angle.
The moving face takes the full Δ, so double the length versus centered.
Same length math. Expansions want the smaller angle because the flow separates.
Compare D against W and H with the same max-Δ / 2 tan θ screen.
Type CFM. V = Q / A at each end. Sudden area ratio still needs a C on fitting-loss.
Shop pattern. Not on this page.
Composite of ranking reducer-length pages. Wall angle, not included angle. Pressure recovery is not this identity.
Estimate only for duct transition length. SMACNA/ASHRAE loss data and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.