Free CFM per room calculator. Split system CFM across rooms by weighted floor area, then count registers at 120 CFM each. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
Ranking room-split tools all start from system airflow = tons × CFM/ton (350 humid / 400 standard / 450 dry), then share that air by floor area times an exposure weight. Interior ~0.8, average 1.0, sunny or corner 1.2, kitchen 1.3. Registers = ceil(room CFM / 120). That is the intersection — not Manual J room loads.
It is not ACCA Manual J or Manual D. A west glass wall still needs a real load.
The ACH/CFM page solves one room from volume. This page splits a system across four rooms so supply-register and duct-size have a CFM to eat.
Related calculators on this site:
Enter tons and 400 CFM/ton, or type system CFM directly. Fill up to four rooms with area and exposure. Example is a 3-ton house with a kitchen factor 1.3.
Tons, CFM/ton chips 350/400/450, optional system CFM, four rooms with ft² and exposure.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
Q_sys = tons × CFM/ton;
Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 3-ton / 400 CFM living + kitchen + two bedrooms.
2) Override system CFM from a blower table.
3) Interior bath at 0.8.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
3 ton × 400 = 1,200 CFM
rooms 320×1, 200×1.3, 180×1, 60×0.8
shares follow the weighted areas; registers at 120 CFM each
It falls out of 400 CFM/ton on about 400 ft²/ton. Exposure weights move rooms off that line.
Humid coils run slower; dry climates push more air. Match the blower, not the climate slogan.
Appliance heat is the reason ranking pages bump kitchens. It is a judgement weight, not a code.
Do not split return CFM the same way. Returns are fewer, larger, and quieter.
Run twice, or treat leftover area as room 4 with factor 1.0.
Comfort band 100–150 CFM per face. 120 sits in the middle of that overlap.
Composite of ranking room-CFM pages: 400 CFM/ton default, area × exposure split, 120 CFM per register. Not a cloned eight-room worksheet.
Estimate only for CFM per room. Manual J room loads and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.