Coil bypass factor Calculator

Free Coil bypass factor calculator. BF = (T_leave − ADP) / (T_enter − ADP); contact factor = 1 − BF; or predict T_leave from BF. Runs in your browser; not a permit or a Manual J.

Updates in this browser · not a mechanical permit


Formula

Identity
BF = (T_leave − ADP) / (T_enter − ADP); CF = 1 − BF; T_leave = ADP + BF(T_enter − ADP)
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

Ranking coil-BF pages all use the straight-line bypass model: leaving air is a mix of air at ADP and untreated entering air. BF = (T_leave − ADP) / (T_enter − ADP). Leave BF blank to compute it from three temperatures, or type BF to predict leaving DB. Contact factor CF = 1 − BF. Typical 4-row ~0.15, 6-row ~0.08 at 500 FPM is talk, not this identity.

It is not an AHRI 410 coil selection and not a psychrometric ADP solver from wet bulbs (that needs the full chart).

Psychrometric gives W and h. This page is only the temperature form of bypass the ranking BF tools share as a field check.

Related calculators on this site:

How to use it

Type entering DB and ADP. Add leaving DB to get BF, or type BF to get leaving DB. Example is 80 / 55 / 52.5 °F.

T_enter, T_leave (or blank), ADP, optional BF.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

BF = (T_leave − ADP) / (T_enter − ADP); CF = 1 − BF; T_leave = ADP + BF(T_enter − ADP)

Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) 80 °F in, 55 °F out, ADP 52.5 °F.

2) Predict leave from BF 0.10.

3) Fouled coil: measured BF much higher than design.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

The Example button uses this set:

80, 55, 52.5 °F

BF = (55−52.5)/(80−52.5) ≈ 0.091

CF ≈ 0.91

FAQ

What is ADP?

Apparatus dew point — the effective saturated coil surface temperature.

BF 0.1 is good?

A 4–6 row wet coil at moderate face velocity often lands 0.05–0.20. Compare to the selection, not a slogan.

Face velocity?

Higher FPM raises BF. This page does not estimate BF from rows; type the measured or selected BF.

Wet-bulb form?

The same ratio holds for W and h if the coil is wet. Entering/leaving DB is the field check.

Leaving RH 90%+?

A wet coil leaves near saturation plus bypass. High leaving RH with a high BF means a lot of untreated air.

Heating coils?

The identity still holds with a different surface temperature. Ranking pages are written for cooling.

References

Composite of ranking BF/ADP pages. Dry-bulb form only; humidity-ratio ADP intersection is a different tool.

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.

Disclaimer

Estimate only for coil bypass factor. Coil software and a licensed designer prevail.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.