Free Coil bypass factor calculator. BF = (T_leave − ADP) / (T_enter − ADP); contact factor = 1 − BF; or predict T_leave from BF. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
Ranking coil-BF pages all use the straight-line bypass model: leaving air is a mix of air at ADP and untreated entering air. BF = (T_leave − ADP) / (T_enter − ADP). Leave BF blank to compute it from three temperatures, or type BF to predict leaving DB. Contact factor CF = 1 − BF. Typical 4-row ~0.15, 6-row ~0.08 at 500 FPM is talk, not this identity.
It is not an AHRI 410 coil selection and not a psychrometric ADP solver from wet bulbs (that needs the full chart).
Psychrometric gives W and h. This page is only the temperature form of bypass the ranking BF tools share as a field check.
Related calculators on this site:
Type entering DB and ADP. Add leaving DB to get BF, or type BF to get leaving DB. Example is 80 / 55 / 52.5 °F.
T_enter, T_leave (or blank), ADP, optional BF.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
BF = (T_leave − ADP) / (T_enter − ADP);
Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 80 °F in, 55 °F out, ADP 52.5 °F.
2) Predict leave from BF 0.10.
3) Fouled coil: measured BF much higher than design.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
80, 55, 52.5 °F
BF = (55−52.5)/(80−52.5) ≈ 0.091
CF ≈ 0.91
Apparatus dew point — the effective saturated coil surface temperature.
A 4–6 row wet coil at moderate face velocity often lands 0.05–0.20. Compare to the selection, not a slogan.
Higher FPM raises BF. This page does not estimate BF from rows; type the measured or selected BF.
The same ratio holds for W and h if the coil is wet. Entering/leaving DB is the field check.
A wet coil leaves near saturation plus bypass. High leaving RH with a high BF means a lot of untreated air.
The identity still holds with a different surface temperature. Ranking pages are written for cooling.
Composite of ranking BF/ADP pages. Dry-bulb form only; humidity-ratio ADP intersection is a different tool.
Estimate only for coil bypass factor. Coil software and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.