Dehumidifier pints Calculator

Free Dehumidifier pints Calculator. a moisture-removal rate in pints/day from airflow and a humidity-ratio drop (or a room ACH sketch). Runs in your browser; not a permit or a Manual J.

Updates in this browser · not a mechanical permit


Formula

Identity
pints/day ≈ ρ × Q × ΔW × 24 h (converted to US pints of water)
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

This page converts a moisture-removal rate in pints/day from airflow and a humidity-ratio drop (or a room ACH sketch). It is the Dehumidifier pints tool in the moisture group on ACH Calculator.

It is not an Energy Star test-condition rating translator or a crawlspace spec. If you need those, open a related tool instead of stretching this identity.

The identity on screen is pints/day ≈ ρ × Q × ΔW × 24 h (converted to US pints of water). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.

Related calculators on this site:

How to use it

Use the fields that match the job: CFM, inlet/outlet W or RH at a T, result pints/day and L/day. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

pints/day ≈ ρ × Q × ΔW × 24 h (converted to US pints of water)

Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) Whole-house 150 CFM, 20 gr/lb drop.

2) Portable unit AHAM pint rating vs this process.

3) Pool dehumidifier.

If the job is life-safety, sterile, or listed equipment, stop here and use the specification.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

The Example button uses this set:

150 CFM

ΔW=20 gr/lb

mass water ≈ 1.9 lb/h → ~4.6 pints/day class — live math

Work the same arithmetic on paper; the live result should match within rounding.

FAQ

AHAM pints?

Rated at 80 °F 60% RH. Your basement 65 °F 60% RH is less. This page is process physics, not the rating.

Grain drop?

Get W from psychrometric at inlet and a coil DP / apparatus dew point at outlet.

L/day?

1 US pint = 0.473 L. SI users may prefer L/day.

Heat from the unit?

Sensible heat of the machine is extra room load. Not subtracted here.

Ventilation vs dehumidifier?

OA can add moisture. ventilation-load latent vs this pint rate.

Oversize?

Short cycles, then RH swings. Match pints to the load.

References

Primary identity: pints/day ≈ ρ × Q × ΔW × 24 h (converted to US pints of water). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.

Disclaimer

Estimate only for Dehumidifier pints. Adopted mechanical codes, OEM curves and a licensed designer prevail.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.