Free Furnace temperature rise calculator. ΔT = supply − return; CFM = output / (1.08 × ΔT); check the nameplate 35–65 °F band. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
Ranking furnace-rise calculators all invert the sensible equation: output = input × AFUE (or clocked input × efficiency), rise = T_supply − T_return after 10–15 minutes, CFM = output / (1.08 × rise). They compare rise to the nameplate min/max (defaults 35–65 °F). 80,000 in × 80% with 118/68 °F → 50 °F and about 1,185 CFM is the example they share.
It is not a combustion-analyzer worksheet. Radiant heat on the supply probe still fools the reading.
Furnace-size picks the next cabinet. This page asks whether the blower is actually moving that air.
Related calculators on this site:
Type input and AFUE, supply and return after a long fire. Example is the 80k / 80% / 50 °F rise set. Leave 35–65 unless the plate says otherwise.
Input BTU/h, AFUE %, T_supply, T_return, nameplate min/max rise.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
output = input × AFUE;
Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 80k input, 80%, 118 °F supply, 68 °F return.
2) Rise above the plate — low airflow.
3) Rise below the plate — extra air or underfired.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
80,000 × 0.80 = 64,000 BTU/h
118 − 68 = 50 °F
CFM = 64,000 / (1.08 × 50) ≈ 1,185
Always output in the CFM identity. Input × AFUE is an estimate of output, not a measured firing rate.
Return before the furnace; supply in the trunk out of sight of the exchanger, after 10–15 minutes.
Too little airflow or overfired. Check filters, ducts, wheel, then gas.
Extra airflow or underfired. High-static ECM furnaces still have a plate range.
Same identity with sensible capacity. Do not put total tons in the numerator.
Thinner air needs more CFM for the same rise. Open air-density; this page is sea-level 1.08.
Composite of ranking rise/CFM pages. Clock the meter if you need a real input. Elevation is omitted.
Estimate only for furnace temperature rise. The rating plate and a licensed technician prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.