Free Window SHGC heat gain calculator. Solar gain q = SHGC × area × irradiance × (1 − shade fraction). Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
Ranking SHGC calculators all multiply the NFRC whole-window SHGC by glass area and an incident irradiance, then knock off a shade fraction. They do not pick the hour for you. Peak vertical irradiance chips 165 south / 200 west / 248 high are the round numbers those pages mention; 200 BTU/h·ft² is the default. 30 ft² at SHGC 0.40 under 200 is 2,400 BTU/h. Conduction U·A·ΔT is not included.
It is not Manual J fenestration with CLTD/SHGF tables and not an NFRC label generator.
AC-size is a whole-house ft²/ton sketch. This page is the west-glass term that sketch forgets.
Related calculators on this site:
Type SHGC from the sticker, area, irradiance chip, shade %. Example is 0.40 × 30 × 200.
SHGC, area ft², irradiance chips 165/200/248, shade %.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
q = SHGC × A × I × (1 − shade)
Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 30 ft² west glass, SHGC 0.40, 200 BTU/h·ft².
2) Compare 0.25 low-E vs 0.70 clear double.
3) 20% overhang shade.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
SHGC 0.40, 30 ft², I=200, shade 0
q = 0.40 × 30 × 200 = 2,400 BTU/h ≈ 0.20 ton
SHGC is the NFRC number. Old SC × 0.87 ≈ SHGC. Do not multiply both.
Orientation and hour. West/east peaks ~200–250 BTU/h·ft²; summer south is often lower because the sun is high.
NFRC SHGC is whole-window. Use the rough opening, not glass-only, unless you have center-of-glass SHGC plus a frame term.
Put the shaded share in the shade box. This page does not draw sun angles.
q/12,000 is a peak solar equivalent, not a compressor size.
Low SHGC that saves August cooling also dumps less free heat in January. Weigh both.
Composite of ranking SHGC×A×I pages. Interior shades are an IAC, not a second SHGC. Peak q is not coincident cooling load.
Estimate only for window solar gain. Full load procedures and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.