Free Heat-pump balance point Calculator. an outdoor-temperature balance point from a linear load line and a linear heat-pump capacity line you type with two points each. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts an outdoor-temperature balance point from a linear load line and a linear heat-pump capacity line you type with two points each. It is the Heat-pump balance point tool in the heat group on ACH Calculator.
It is not a bin-hour cost model, defrost, or a utility dual-fuel tariff. If you need those, open a related tool instead of stretching this identity.
The identity on screen is Intersect q_load = k (T_in − T_out) with q_hp = q0 + m (T_out − T_ref). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: Load at two T_out, HP capacity at two T_out, indoor T, result T_balance. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
Intersect q_load = k (T_in − T_out) with q_hp = q0 + m (T_out − T_ref)
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) Load 60k at 0 °F, 0 at 65 °F; HP 20k at 0, 36k at 47.
2) Finding strip-heat need below T_bp.
3) Dual fuel lockout talk.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
Solve T where q_load(T)=q_hp(T)
Work the same arithmetic on paper; the live result should match within rounding.
Loads are roughly linear in ΔT. Heat-pump capacity is not perfectly linear — two-point is a sketch.
Cuts average capacity. Knock the capacity points down if you want.
Below T_bp, gap = load − HP. Strips or furnace.
Use rated capacities at 17 °F and 47 °F as your two points.
Not this page.
Still required for equipment.
Primary identity: Intersect q_load = k (T_in − T_out) with q_hp = q0 + m (T_out − T_ref). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.
Estimate only for Heat-pump balance point. Adopted mechanical codes, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.