Free ASHRAE 62.2 Calculator. a dwelling mechanical ventilation rate using the ASHRAE 62.2 floor-area plus bedroom count identity. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts a dwelling mechanical ventilation rate using the ASHRAE 62.2 floor-area plus bedroom count identity. It is the ASHRAE 62.2 tool in the air group on ACH Calculator.
It is not room ACH, bath 50 CFM, or 62.1 occupancy outdoor air for a classroom. If you need those, open a related tool instead of stretching this identity.
The identity on screen is Q_fan = 0.03 A_floor + 7.5 (N_br + 1) (62.2-2016 IP form). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: Conditioned floor area, bedroom count, optional infiltration credit (user), units ft²/m². Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
Q_fan = 0.03 A_floor + 7.5 (N_br + 1) (62.2-2016 IP form)
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) A 2,000 ft², 3-bedroom house: 0.03×2000 + 7.5×4 = 90 CFM.
2) A small apartment with 1 bedroom.
3) Comparing 62.2 CFM with ACH50-derived infiltration.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
A = 2000 ft²
N_br = 3
Q = 0.03×2000 + 7.5×(3+1) = 60 + 30 = 90 CFM
Work the same arithmetic on paper; the live result should match within rounding.
The printed identity is the widely posted 62.2-2013/2016 IP form. Later addenda, local adoptions and infiltration credits differ. This is not a compliance stamp.
The standard uses occupants ≈ bedrooms + 1 as a default occupancy for the 7.5 CFM/person term.
62.2 is a required outdoor-air rate. ERV, exhaust-only, or supply-only are system choices; this page only sizes the rate.
If you type a credit, it is subtracted as you entered it. ACH50 → natural ACH is a separate sketch.
The SI 62.2 form uses 0.15 L/s·m² plus 3.5 L/s per person. Toggle units.
Only if it actually runs enough hours and the dwelling rate is ≤ 50 CFM. Intermittent bath exhaust is not automatically whole-house ventilation.
Primary identity: Q_fan = 0.03 A_floor + 7.5 (N_br + 1) (62.2-2016 IP form). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.
Estimate only for ASHRAE 62.2. Adopted mechanical codes, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.