Ranking bathroom-fan calculators overlap on a governing CFM, not a single line. IMC-style discussion still starts at about 50 CFM intermittent or 20 CFM continuous for a dwelling bath. HVI-style pages add floor-area and fixture counts (toilet, shower, tub, jetted tub). Large rooms also get an 8 ACH check: CFM_8 = Volume × 8 / 60. The fan you buy is the next common size (50, 80, 110, 150…) at or above the governing number.
Example on this site: 10 × 8 × 8 ft bath, one toilet, one shower. Area 80 ft². Code floor 50 CFM. HVI area/fixture talk often lands near 80 CFM. 8 ACH on 640 ft³ is 85 CFM. Governing 85 CFM, next common fan 110 CFM. That 110 is still a nameplate at a test pressure; elbows and a roof cap cut delivered CFM.
What not to do
Do not size a powder room as 6 ACH on the room-ACH chart and install a 30 CFM computer fan. Do not add every bath’s 50 CFM into 62.2. Do not treat a jetted tub like a toilet. Open bathroom fan for the combined check, then makeup air if many baths plus a hood can run together.
FAQ
Intermittent or continuous?
Intermittent is a switch-operated ~50 CFM fan. Continuous is a low-sone always-on ~20 CFM fan. Do not add them unless the design says so.
Does 50 CFM include duct loss?
Nameplate CFM is at a rated static. Long ducts need a higher nameplate or a quieter in-line fan. Open static pressure / fan-actual.
Toilet-only rooms?
Some tables list a lower rate. Confirm the adopted IMC/IRC year. This tool still lets you type fixture counts.
Glass shower?
Still usually one dwelling bath for the table unless the spec splits rooms.
Makeup air for one bath?
Rarely. Stack several baths, a dryer and a 400+ CFM hood, then check makeup.
Limits
Not a locker-room, not a hospital soiled-utility exhaust, not a listed explosion-proof fan.
Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.