Free CO₂ ventilation calculator. Outdoor CFM per person = CO₂ generation / ((indoor ppm − outdoor ppm) / 1,000,000). Runs in your browser; not a permit.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
Ranking CO₂ ventilation calculators use the steady-state balance: airflow per person equals CO₂ generation divided by the indoor-to-outdoor difference as a fraction. The sedentary generation they share is about 0.0106 CFM of CO₂ per person (0.005 L/s). 1,100 ppm indoors against 400 ppm outdoors is the classic 15.1 CFM per person.
Not the ASHRAE 62.1 people-and-area table. CO₂ only tracks occupant dilution after the room has settled.
The outdoor-air page on this site is Rp × people + Ra × area. This page backs a CFM out of a CO₂ setpoint.
Related calculators on this site:
Type people, indoor ppm, outdoor ppm and CO₂ generation per person. Example is 20 people, 1,100 ppm, 400 ppm, 0.0106 CFM.
People, indoor ppm, outdoor ppm, CO₂ generation CFM per person.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
Q/person = G / ((C_in − C_out) / 10^6);
Indoor ppm must be above outdoor ppm. Generation and people must be positive. A rising reading is not this steady state.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 20 people held at 1,100 ppm with 400 ppm outdoors.
2) The same room tightened to 1,000 ppm.
3) A lower generation, 0.0084 CFM, for quieter sedentary work.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
0.0106 / ((1,100 − 400) / 10^6) = 15.1 CFM per person
20 × 15.1 = 303 CFM
Sedentary adult those pages default. Body size, age and activity change it. 0.005 L/s is the same number.
Either is a setpoint you type. 1,100 − 400 with 0.0106 CFM is 15.1 CFM per person. A tighter setpoint needs more air.
Then the room is not at steady state. A climbing reading makes this method understate the ventilation you already have.
Type a measured outdoor value. 400–420 ppm is what the ranking pages preload.
No. 62.1 is the design minimum from people and floor area. This is the airflow that holds a CO₂ number.
Both. Total is per person times the headcount. An empty room is not this equation.
Composite of ranking CO₂ ventilation calculators. Generation 0.0106 CFM per sedentary person is the preload those pages share. 0.005 L/s is the same quantity.
Estimate only for a steady, well-mixed room. It does not measure other pollutants and it does not replace a ventilation-rate design.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.