Free Pipe friction (Hazen–Williams) calculator. Water friction hf/100 ft = 0.2083 (100/C)^1.852 Q^1.852 / d^4.8655, plus velocity. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
Ranking hydronic friction calculators use Hazen–Williams in IP water units, not Darcy–Weisbach, because that is what sprinkler and hydronic worksheets share: hf per 100 ft = 0.2083 × (100/C)^1.852 × Q^1.852 / ID^4.8655. C chips 150 PVC / 140 copper / 130 steel / 120 aged. Velocity 0.4085 GPM / ID² sits next to it so you can still respect the 4 fps copper talk on hydronic-pipe. psi = ft / 2.31.
It is not a glycol viscosity correction and not a fitting-equivalent table (add those feet into L).
Hydronic-pipe picks Type L copper from a 4 fps cap. This page reports the feet of head that copper (or steel, or PVC) actually spends.
Related calculators on this site:
Type GPM, inside diameter, C chip, length. Example is 15 GPM in 1 in Sch 40 (ID 1.049) at C 130, 100 ft.
GPM, ID inches, C chips 150/140/130/120, length ft.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
hf/100 ft = 0.2083 (100/C)^1.852 Q^1.852 / d^4.8655;
Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 15 GPM, 1.049 in ID, C=130, 100 ft.
2) Compare C 140 copper vs C 120 aged steel.
3) Feed pump-head with hf × circuit.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
15 GPM, ID 1.049, C=130, L=100
hf/100 from Hazen–Williams; V from 0.4085 Q/ID²
New copper often 140–150 on those pages. 140 is the conservative chip here.
Hazen–Williams wants inside diameter. 1 in Sch 40 steel is 1.049 in, not 1.000.
Closed hydronic pumps are in feet. psi = ft / 2.31 for water.
Hazen–Williams is a water equation. Use Darcy–Weisbach with the right viscosity, or a manufacturer chart.
Add equivalent length into L. This page is straight pipe plus whatever length you typed.
HW was fitted on larger water mains. Small-tube hydronic is still what ranking HVAC pages run.
Composite of ranking Hazen–Williams pages. Valid for water near 60 °F; hydronic 140–180 °F is a bit optimistic (lower viscosity).
Estimate only for water pipe friction. Hot-water viscosity, glycol and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.