Hydronic System Volume Calculator

Free hydronic volume calculator. Gallons = pipe length × gallons per foot + emitters + boiler. A glycol percent splits that total.

Updates in this browser · not a mechanical permit


Formula

Identity
system = length × gal/ft + emitters + boiler; glycol = system × percent / 100; water = system − glycol
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

This page adds up the water in a hydronic loop. Pipe gallons are length times gallons per foot. Emitters and the boiler are gallons you already know. A percent then splits the total into glycol concentrate and water. Three-quarter-inch copper is about 0.025 gallons per foot, which is 2.5 gallons per 100 ft.

Not a pipe-size chart, and not a freeze-point chart. Type gallons per foot for the pipe you have. The expansion-tank page starts from the total gallons.

The chip is 0.025 gal/ft for 3/4 in copper. Cast-iron radiation is often about 1.6 gallons per square foot of EDR, fin-tube about 0.05 gallons per foot, a cast-iron boiler about 10 gallons, and a wall-hung boiler about 2 gallons. Those are round figures, so this page asks for gallons.

Related calculators on this site:

How to use it

Type pipe length, gallons per foot, emitter gallons, boiler gallons, and the glycol percent. The example is 200 ft of 3/4 in copper, 64 gallons in the radiators, a 10 gallon boiler, and 30 percent glycol.

Pipe ft, gal/ft, emitter gal, boiler gal, glycol %.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

system = length × gal/ft + emitters + boiler; glycol = system × percent / 100; water = system − glycol

Length and gallons per foot must be positive. Emitter and boiler gallons may be zero. Glycol percent runs from 0 to 100.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) 200 ft at 0.025 gal/ft, 64 gal of emitters, a 10 gal boiler, 30 percent glycol.

2) 500 ft at the same 0.025, 8 gal of terminals, a 5 gal boiler, 30 percent.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

200 × 0.025 = 5 gal of pipe. 5 + 64 + 10 = 79 gal. Thirty percent of 79 is 23.7 gal of concentrate, and the rest is 55.3 gal of water.

Another loop, 500 × 0.025 + 8 + 5 = 25.5 gal, is about 7.7 gal of concentrate and about 17.9 gal of water at 30 percent.

FAQ

Why 0.025?

That is about 2.5 gallons in 100 ft of 3/4 in copper. Other sizes differ, so type the gallons per foot for the pipe you have.

Why 79 gallons?

200 ft × 0.025 = 5. Forty square feet of cast iron at about 1.6 gal per sq ft of EDR is 64. A cast-iron boiler is about 10. 5 + 64 + 10 = 79.

Why 23.7 gallons of glycol?

Thirty percent of 79 is 23.7 gallons of concentrate. The other 55.3 gallons are water.

What about 25.5 gallons?

500 ft × 0.025, plus 8 gallons of terminals and a 5 gallon boiler. At 30 percent that is about 7.7 gallons of concentrate and about 17.9 gallons of water.

Where do the emitter gallons come from?

Cast iron is often about 1.6 gallons per square foot of EDR, and the pattern can run about 1.3 to 2.0. Fin-tube is about 0.05 gallons per foot. A cast-iron boiler is about 10 gallons, and a wall-hung boiler about 2.

Why does the expansion tank need this?

The tank has to absorb the expansion of this water. The expansion-tank page starts from the gallons you enter there.

References

3/4 in copper is about 0.025 gal/ft. System volume is pipe plus emitters plus boiler. Glycol gallons are that total times the percent.

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.

Disclaimer

Estimate only. Measure what you pour when the charge has to be exact. Radiator water content changes with the pattern.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.