Free Commercial kitchen hood calculator. Type I unlisted wall or island canopy: Q = hood length × CFM per foot by cooking duty. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
Ranking commercial-hood calculators converge on IMC unlisted canopy rates by linear foot, not the residential 100/150 CFM/ft page. Wall-mounted canopy: 200 light / 300 medium / 400 heavy / 550 extra-heavy. Island canopy: 400 / 500 / 600 / 700. The heaviest appliance under the hood sets the rate. Makeup at ~80% of exhaust is the planning note they all add. Listed hoods use the listing instead.
It is not a listed-hood UL 710 worksheet, not NFPA 96, and not the residential kitchen-hood page.
Kitchen-hood is the home 100/150 CFM/ft plus BTU/100 rule. This page is the commercial linear-foot schedule.
Related calculators on this site:
Type hood length in feet, wall vs island, duty of the heaviest appliance. Example is 10 ft wall, medium (fryers/griddles) = 3,000 CFM.
Hood length ft, wall vs island, duty light/medium/heavy/extra-heavy.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
Q = L_hood × CFM/ft (wall 200/300/400/550;
Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 10 ft wall canopy over fryers (medium → 300 CFM/ft).
2) Island over a charbroiler (heavy).
3) Solid fuel extra-heavy 550/700.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
10 ft wall, medium duty
Q = 10 × 300 = 3,000 CFM
makeup talk 80% = 2,400 CFM
Ovens/steamers light; ranges/fryers/griddles medium; charbroilers/woks heavy; solid fuel extra-heavy — the duty names those pages share.
Use the listed exhaust. These rates are the unlisted canopy floor.
Heat and moisture without grease. Not this page’s Type I schedule.
Planning pages show 80–90% so the kitchen stays slightly negative. IMC still wants makeup approximately equal to exhaust from all sources.
Code overhang lengthens the hood; type the actual hood length, not the appliance length.
A check, not the sizing method these ranking pages use. Linear foot × duty is the code sketch.
Composite of ranking IMC hood-CFM pages. Overhang, backshelf and Type II dishwasher 100 CFM/ft are out of scope.
Estimate only for unlisted commercial hoods. IMC 507, the listing and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.