Moist air at a known barometric pressure is fixed by two properties. The usual pair on this site is dry-bulb temperature plus relative humidity. Saturation vapor pressure follows a Magnus / WMO-style exponential in Celsius; partial pressure is RH/100 × e_s; humidity ratio is W = 0.622 e / (P − e); dew point inverts Magnus from e; enthalpy is h ≈ 1.006 t + W (2501 + 1.86 t) kJ/kg with t in °C. Wet bulb is iterated so enthalpy matches saturation at T_wb.

If you measured dew point (a window condensation job), open RH with DB + DP instead of inventing an RH. If you have DB + RH and need grains for a latent load, open humidity ratio then latent heat. If you need coil leaving-air, you still need a coil model — these pages are states, not coils.

Worked numbers

75 °F dry bulb, 50% RH is a common indoor talk: dew point near 55 °F, humidity ratio near 64 gr/lb at standard P. Pulling that air to 55 °F dew point at a coil is a latent job; blowing 55 °F dew-point air at a 50 °F window is still a condensation risk.

FAQ

Why not paste an ASHRAE chart?

The chart is copyrighted. The identities are not a photocopy of the chart.

Altitude?

P in the W formula should fall with altitude. Open air-density for P, then treat W as approximate if you leave P at sea level.

Wet bulb versus dew point?

Dew point is the saturation temperature at the actual vapor pressure. Wet bulb includes evaporative cooling. They match only at 100% RH.

Grains versus kg/kg?

7000 grains = 1 lb. IP latent uses grains; SI uses kg/kg.

Refrigerant p-h?

Wrong chart. These pages are moist air.

Limits

Not a process-air dryer spec and not a pharmaceutical humidity validation.

Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.