Condensate drain size Calculator

Free Condensate drain size calculator. Single unit 3/4 in floor; manifolded lines by combined tons; 1/8 in/ft slope; GPH from latent. Runs in your browser; not a permit or a Manual J.

Updates in this browser · not a mechanical permit


Formula

Identity
single ≥ 3/4 in; manifold 3/4–2 in by combined tons; slope 1/8 in/ft
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

Ranking drain calculators agree: a single, non-manifolded unit never goes below 3/4 in and never smaller than the pan outlet. When two or more units share a line, they look up combined tons: ≤20 → 3/4, ≤40 → 1, ≤90 → 1-1/4, ≤125 → 1-1/2, ≤250 → 2. Slope 1/8 in/ft. GPH ≈ tons × 12,000 × (1−SHR) / 8,840 is the latent sketch they add.

It is not a trap-height manufacturer drawing and not a condensing-furnace neutralization spec.

Cooling-tons is capacity. This page is the pipe that carries the water that capacity condensed.

Related calculators on this site:

How to use it

Type tons, single vs manifolded, pan outlet, run length, SHR. Example is a 3-ton single unit, 20 ft run, SHR 0.75.

Tons, single/manifolded, pan outlet in, run ft, SHR.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

single ≥ 3/4 in; manifold 3/4–2 in by combined tons; slope 1/8 in/ft

Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) 3-ton furnace coil, single 3/4 in.

2) Two 12-ton RTUs manifolded.

3) Long run fall at 1/8 in/ft.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

The Example button uses this set:

3 ton, single, pan 0.75 in, 20 ft, SHR 0.75

pipe 3/4 in; drop 2.5 in; GPH ≈ 1.0

FAQ

Why always 3/4 on one unit?

That is the code floor ranking pages all quote, even on a 20-ton single. The pan outlet can be larger — never shrink.

Manifold traps?

Each pan gets its own trap before the shared line. A shared trap lets one blower pull through another pan.

SHR 0.75?

A planning latent split. Wet coils in humid rooms make more water; type a lower SHR.

1/8 or 1/4 in/ft?

1/8 in/ft (1%) is the mechanical-code slope those pages share. Steeper is fine; flatter sags into a trap.

PVC schedule?

Material is a code list. Size is this page.

Secondary drain?

A second pan outlet, not a second size table.

References

Composite of ranking IMC 307.2.2 drain pages. Trap depth stays with the OEM. Acidic furnace condensate is a different material rule.

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.

Disclaimer

Estimate only for condensate drain size. IMC 307 / UPC and the pan outlet govern.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.