Free Condensate drain size calculator. Single unit 3/4 in floor; manifolded lines by combined tons; 1/8 in/ft slope; GPH from latent. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
Ranking drain calculators agree: a single, non-manifolded unit never goes below 3/4 in and never smaller than the pan outlet. When two or more units share a line, they look up combined tons: ≤20 → 3/4, ≤40 → 1, ≤90 → 1-1/4, ≤125 → 1-1/2, ≤250 → 2. Slope 1/8 in/ft. GPH ≈ tons × 12,000 × (1−SHR) / 8,840 is the latent sketch they add.
It is not a trap-height manufacturer drawing and not a condensing-furnace neutralization spec.
Cooling-tons is capacity. This page is the pipe that carries the water that capacity condensed.
Related calculators on this site:
Type tons, single vs manifolded, pan outlet, run length, SHR. Example is a 3-ton single unit, 20 ft run, SHR 0.75.
Tons, single/manifolded, pan outlet in, run ft, SHR.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
single ≥ 3/4 in;
Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 3-ton furnace coil, single 3/4 in.
2) Two 12-ton RTUs manifolded.
3) Long run fall at 1/8 in/ft.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
3 ton, single, pan 0.75 in, 20 ft, SHR 0.75
pipe 3/4 in; drop 2.5 in; GPH ≈ 1.0
That is the code floor ranking pages all quote, even on a 20-ton single. The pan outlet can be larger — never shrink.
Each pan gets its own trap before the shared line. A shared trap lets one blower pull through another pan.
A planning latent split. Wet coils in humid rooms make more water; type a lower SHR.
1/8 in/ft (1%) is the mechanical-code slope those pages share. Steeper is fine; flatter sags into a trap.
Material is a code list. Size is this page.
A second pan outlet, not a second size table.
Composite of ranking IMC 307.2.2 drain pages. Trap depth stays with the OEM. Acidic furnace condensate is a different material rule.
Estimate only for condensate drain size. IMC 307 / UPC and the pan outlet govern.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.