HVAC airflow, ACH and duct calculators

Type a room, a hood, a duct or a coil. The math stays in this browser. These are published HVAC identities — not a permit, not Manual J, and not a listed-hood submittal.

Quick convert

Fill length, width, height and either ACH or CFM. The other solves. Open a full tool for hoods, 62.2 and ducts.

Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

All calculators

Air

ACH to CFMRoom air changes per hour into supply or exhaust airflow in cubic feet per minute (and the reverse).Bathroom fan CFMA residential bathroom exhaust rate using the IMC-style 50/20 CFM chips or a volume×ACH check.Range hood CFMRange-hood airflow from hood length, face velocity, or a typed CFM — not from kitchen ACH.ASHRAE 62.2A dwelling mechanical ventilation rate using the ASHRAE 62.2 floor-area plus bedroom count identity.ASHRAE 62.1 OABreathing-zone outdoor air from 62.1 people and area rates you type (Rp, Ra, Pz, Az).Makeup airHow much dedicated makeup airflow you still need after subtracting the exhaust you typed and an allowed uncompensated amount.Garage exhaustA residential or small garage exhaust sketch from ACH or CFM per square foot.Attic ventilationA net-free attic ventilation area sketch using 1/150 or 1/300 of attic floor area.Cleanroom ACHCleanroom supply CFM from a user-selected air-change target associated with an ISO class name.Grow tent CFMGrow-tent exhaust from tent volume, a target air-change rate, and an optional carbon-filter derate.CADR air changesAir-cleaner air changes from AHAM-style CADR and room volume (or the reverse CADR need).ACH50 to ACHA crude natural infiltration estimate from a blower-door ACH50 and a user n-factor.Parking garage CFMAn enclosed parking-garage exhaust sketch from ACH or CFM per area — with CO demand-control called out as not modeled.CFM per roomSplit system CFM across rooms by weighted floor area, then count registers at 120 CFM each.Commercial exhaust CFMRoom exhaust from a user-typed per-fixture or per-area rate — not a reprinted occupancy table.Commercial kitchen hoodType I unlisted wall or island canopy: Q = hood length × CFM per foot by cooking duty.Dryer exhaust and makeupAdd dryer + hood + baths that can run together; flag makeup when the hood > 400 or the dryer > 200 CFM.Whole-house fanCFM = floor area × CFM/ft², scaled by ceiling height over 8 ft. Attic net free area is CFM/750.Evaporative coolerCFM = (floor area × ceiling height) / minutes per air change.Attic fanCFM = attic floor × 0.7, or × 0.805 for a dark or steep roof.CO₂ to CFMOutdoor CFM per person = generation / ((indoor ppm − outdoor ppm) / 1,000,000).ERV / HRV heatVentilation from floor area and bedrooms, then recovered heat = 1.08 × CFM × ΔT × effectiveness.

Duct

Duct sizeRound or rectangular duct size from CFM and a target velocity, or from a user equal-friction rate.Duct velocityMean duct velocity from airflow and cross-section (round diameter or W×H).Equivalent round ductHuebscher equivalent round diameter of a rectangular duct so friction comparisons stay honest.Duct frictionStraight-duct pressure drop from a typed friction rate or a Darcy-Weisbach sketch with user roughness.Fitting lossA fitting pressure drop from a user loss coefficient C and velocity (dynamic pressure).Duct offsetThe centerline length and run of a duct offset given rise and fitting angle — HVAC geometry, not electrical conduit.Static pressureA fan external static budget by adding the pressure drops you type.Total equivalent lengthPressure drop from total equivalent length and a friction rate — the residential TEL method.Duct aspect ratioAspect ratio of a rectangular duct and the equivalent diameter penalty as AR grows at constant area.SCFM to ACFMActual cubic feet per minute from standard CFM using the temperatures and pressures you type.Air densityMoist or dry air density from temperature, pressure or altitude so 1.08 and fan power stay honest.Return grille sizeReturn (or supply) grille size from CFM, face velocity, and a free-area fraction.Supply register sizeStock floor or ceiling register from room CFM, face velocity and free-area share.Friction rate from ESPAvailable static pressure after coil, filter and fittings, then FR = ASP × 100 / TEL.Duct transition lengthMinimum centered reducer length from wall angle: L = max(ΔW, ΔH)/2 / tan(θ).

Fan

Heat

Sensible heatSensible heating or cooling rate of an airstream from CFM and dry-bulb difference.Latent heatLatent cooling (or humidification) rate from airflow and a humidity-ratio difference.Mixed-air temperatureMixed-air dry bulb (and optional humidity ratio) from two airstreams, typically OA and return.BTU to CFMRequired airflow from a sensible BTU/h and a temperature difference (inverse of 1.08).Cooling tonsCooling tons from BTU/h or kW, and the reverse.CFM per tonAirflow from cooling tons using the 400 CFM/ton family of rules you can edit.AC sizeA crude residential air-conditioner capacity from floor area — labeled as not Manual J.Heating loadA crude winter heating load from area and a user BTU/h·ft² or a UA×ΔT sketch.Furnace sizeFurnace input and output from a heating load and AFUE (and an optional oversize pickup).Heat-pump sizeA comparison of cooling tons and heating BTU/h so you can see which one governs a heat-pump pick.Mini-split BTUA room-level ductless capacity sketch from area and a BTU/h per square foot chip.Chiller tonnageEvaporator (or condenser) tons from chilled-water flow and ΔT.Ventilation loadOutdoor-air sensible plus latent load from OA CFM and indoor/outdoor psychrometric states.Heat-pump balance pointAn outdoor-temperature balance point from a linear load line and a linear heat-pump capacity line you type with two points each.Makeup-air heatingWinter MAU output q = 1.08 × CFM × (T_supply − T_outdoor) × share.Furnace temperature riseΔT = supply − return; CFM = output / (1.08 × ΔT); check the nameplate 35–65 °F band.Window SHGC heat gainSolar gain q = SHGC × area × irradiance × (1 − shade fraction).AC running costWatts = BTU/h ÷ the efficiency number. Cost = kW × hours × duty × your price.Combustion air openingFree area per opening = input ÷ the rate you pick. Gross opening divides by the louver’s free area.Baseboard lengthElectric feet = (BTU/h ÷ 3.412) ÷ W/ft. Hot-water feet = BTU/h ÷ the element’s BTU/h per foot.Baseboard from the roomWatts = room area × W/ft². Length = watts / 250.

Moisture

Water

What this calculator does

This page converts a room’s air changes per hour to airflow in CFM, and the reverse. Fill length, width and height (or a volume), then type ACH or CFM; the other quantity solves. The identity is CFM = ACH × volume / 60.

Bathroom 50/20 CFM, whole-house 62.2, occupancy 62.1, kitchen hoods, ducts, coils and hydronic GPM are separate tools. Fire/smoke and health-care ventilation follow those specifications, not this room box.

How to use it

Enter dimensions and either ACH or CFM. Example loads a 12×14×8 ft room at 6 ACH (134.4 CFM). Open a card below when the job is a hood, a duct, a coil or water flow.

Unit chips switch feet/metres and CFM, m³/h or L/s. Related tools reuse the last airflow and temperatures you typed on this device.

Formula, units, and limits

CFM = ACH × L × W × H / 60 with feet and minutes. In SI, Q in m³/h = ACH × V with metres, because ACH is already per hour.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Use this when you have a box and an air-change target. Use bathroom-fan or kitchen-hood when the talk is an exhaust table. Use whole-house for 62.2 and outdoor-air for 62.1.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

12 × 14 × 8 ft → 1344 ft³. At 6 ACH: 6 × 1344 / 60 = 134.4 CFM (about 228 m³/h).

The same box at 0.35 ACH is only 7.8 CFM. That is why dwelling ventilation and a bath fan are different pages.

FAQ

Is 6 ACH a code value?

No. It is the example. Offices, baths, tents and cleanrooms use different ranges. Open the room-ACH chart, then come back.

Does this size a bath fan?

Only as a volume check. Intermittent 50 CFM and continuous 20 CFM live on the bathroom-fan page.

Can I enter metres?

Yes. Switch the SI chips; the algebra is the same.

Does ACH here include infiltration?

No. This is mechanical air changes of the typed volume. ACH50 is a separate infiltration sketch.

Where do I go next?

Take the CFM to duct size, a hood, makeup air, or 62.1/62.2 if that is the job.

Is this a load calculation?

No. Sensible heat 1.08 and tons are in the heat group. This page is volume and air changes only.

References

Disclaimer

A room ACH sketch is not a permit, a Manual J, or a listed-hood rating.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size combustion air, refrigerant charge, fire dampers, medical gas, or electrical conductors.