Humidifier gallons per day Calculator

Free Humidifier gallons per day calculator. Winter GPD from infiltration CFM and indoor-minus-outdoor humidity ratio (grains). Runs in your browser; not a permit or a Manual J.

Updates in this browser · not a mechanical permit


Formula

Identity
CFM = ACH×V/60; GPD = CFM×60×0.075×Δgr/7000×24/8.34
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

Ranking humidifier sizers follow AHRI-style infiltration: CFM = ACH × volume / 60 with tightness chips 0.5 tight / 1.0 average / 1.5 loose, indoor 70 °F at a target RH (35% on a 20 °F day is the glass-fog chart they share), outdoor 70% RH at the design dry-bulb. Water = air lb/h × Δgrains / 7000; GPD = lb/h × 24 / 8.34. A 2,000 ft² × 8 ft average house at 20 °F is the example they all run.

It is not an evaporative-humidifier 120 °F plenum rating and not a steam-rod kW pick.

Dehumidifier is summer latent removal. This page is winter moisture you must add to the air that leaks in.

Related calculators on this site:

How to use it

Type floor area, ceiling, tightness chip, indoor T/RH and outdoor T/RH. Example is 2,000 ft², 8 ft, 1.0 ACH, 70/35 in, 20/70 out.

Area, height, ACH chips 0.5/1.0/1.5, T_in, RH_in, T_out, RH_out.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

CFM = ACH×V/60; GPD = CFM×60×0.075×Δgr/7000×24/8.34

Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) 2,000 ft² average house, 20 °F design.

2) Tight 0.5 ACH with HRV still dumping dry air — add that CFM to ACH.

3) Compare 35% vs 40% indoor RH.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

The Example button uses this set:

2,000×8, ACH=1 → 267 CFM

Δgrains from 70 °F/35% vs 20 °F/70%

GPD from the infiltration identity

FAQ

Tight / average / loose?

AHRI-style 0.5 / 1.0 / 1.5 ACH chips ranking sizers share. Blower-door ACH50/N is better if you have it.

Why 35% at 20 °F?

Window condensation. Warmer glass or better U-factor can hold more RH.

Pints vs gallons?

US portable units use pints/day (8 pints = 1 gallon). Whole-house ratings are GPD at a stated plenum temperature.

Ventilation CFM?

Add continuous exhaust or ERV outdoor air into the ACH/CFM. Infiltration alone understates a tight, ventilated house.

Steam vs bypass?

Load is the same. Output ratings are not — bypass evaporative numbers assume hot air and a blower that never stops.

Outdoor 70% RH?

Winter air at 20 °F is often near saturation. Type a drier RH if you have design data.

References

Composite of ranking GPD humidifier pages. People/cooking credits are omitted on purpose (those pages call them 1–2 gal/day of free moisture).

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.

Disclaimer

Estimate only for humidifier load. AHRI Guideline F, glass-fog limits and a licensed designer prevail.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.