Free Friction rate from ESP calculator. Available static pressure after coil, filter and fittings, then FR = ASP × 100 / TEL. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
Ranking Manual D friction-rate pages all do two subtractions: ASP = blower ESP minus coil, filter, registers and other external drops; TEL = longest supply plus longest return equivalent length; FR = ASP × 100 / TEL in inches w.c. per 100 ft. They also flag the 0.06–0.18 working band. Defaults 0.5 ESP, 0.20 coil, 0.10 filter, 0.06 terminals, 150+100 ft TEL are the numbers those pages repeat.
It is not a fitting-equivalent-length table and not a blower curve. Type OEM drops at your airflow.
The duct-friction page spends a rate you already know. This page is how that rate is born from the blower budget.
Related calculators on this site:
Leave ESP at 0.5 unless the fan table says otherwise. Subtract only losses outside the rating boundary. Example uses 0.36 in of components over 250 ft TEL.
ESP, coil ΔP, filter ΔP, other ΔP, supply TEL, return TEL.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
ASP = ESP − ΣΔP;
Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 0.5 in ESP, wet coil 0.20, filter 0.10, 0.06 terminals.
2) Negative ASP — components ate the blower.
3) Short ducts that push FR above 0.18.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
ESP=0.5; coil 0.20; filter 0.10; other 0.06
TEL=150+100=250 ft
ASP=0.14; FR=0.056 in/100 ft
Straight duct plus fitting equivalent lengths on the controlling supply path plus the controlling return path. Parallel branches are not added.
A field habit. This page derives the rate instead of assuming 0.08.
If the fan table already includes the coil, do not subtract it again.
The components consume the blower. Change the filter, coil, route, or equipment before sizing duct.
The working window ranking Manual D pages all cite. Below 0.06 the ducts get huge; above 0.18 they get noisy.
Diagnosis, not design. Design uses rated ESP at the design CFM.
Composite of ranking ASP÷TEL calculators. Component drops are user-typed, not reprinted from Manual D tables.
Estimate only for friction rate from ESP. ACCA Manual D, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.