Free Boiler size Calculator. boiler input from a heating load and efficiency, plus a first-cut GPM at the ΔT you type. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts boiler input from a heating load and efficiency, plus a first-cut GPM at the ΔT you type. It is the Boiler size tool in the water group on ACH Calculator.
It is not a gas-pipe size, venting category, or radiation EDR table reprint. If you need those, open a related tool instead of stretching this identity.
The identity on screen is Input = Load / η; GPM = q / (500 ΔT). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: Load BTU/h, η or AFUE, ΔT, result input and GPM. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
Input = Load / η;
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 80 kBTU/h load, 92% condensing.
2) 180 °F reset vs 140 °F.
3) Old 30 °F ΔT vs modern 20 °F.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
Load=80,000
η=0.92
Input=87,000
ΔT=20 → GPM=8.0
Work the same arithmetic on paper; the live result should match within rounding.
Type nameplate thermal efficiency if you have it; AFUE is seasonal.
Short cycling on a boiler is as real as on a furnace. Buffer tanks are a system choice.
EDR and 240 BTU/h·ft² steam talk is not this water formula.
Add the DHW BTU/h the vendor lists, or a user recovery load.
Cast-iron often 20–30 °F. Low-mass condensing may use a larger ΔT. You type it.
furnace-size is airside AFUE.
Primary identity: Input = Load / η; GPM = q / (500 ΔT). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.
Estimate only for Boiler size. Adopted mechanical codes, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.