Aria
CFM = ACH × Volume / 60Ricambi in CFMAprirequired = max(50 CFM code floor, HVI area or fixtures, 8 ACH); buy next common fanAspiratore bagnoApriQ = max(100 CFM, 100 or 150 CFM/ft × width, BTU/h ÷ 100); flag makeup air if Q > 400Cappa cucinaApriQ_vent = 0.03 A_floor + 7.5 (N_br + 1) (ASHRAE 62.2 form, IP)ASHRAE 62.2ApriV_bz = Rp × Pz + Ra × Az (ASHRAE 62.1 breathing-zone form)Aria esterna 62.1Apriif Q_exh > 400 CFM then Q_mu ≈ Q_exh, else 0 (IRC talk; not Q_exh − 400)Aria di reintegroApriCFM = ACH × V / 60 or CFM = cfm/ft² × AEstrazione garageApriA_net ≈ A_attic / 150 (or /300); split 50/50 intake/exhaust NFA in in²Ventilazione sottotettoApriCFM = ACH_ISO × V / 60 (ACH from user ISO class pick or custom)ACH camera biancaApriQ = V × exchanges/min × (1 + filter%) × lights (1/min is the common tent sketch)Portata grow tentApriACH = CADR × 60 / V; also CADR_5ACH = V × 5 / 60CADR ricambiApriACH_nat ≈ ACH50 / N; CFM_nat ≈ CFM50 / N (N chips 20/16/13)ACH50 in ACHApriCFM = ACH × V / 60 or CFM = cfm/ft² × AAutorimessaApriQ_sys = tons × CFM/ton; Q_room = Q_sys × (A×f) / Σ(A×f)CFM per stanzaApriQ = n × CFM/unit or Q = A × CFM/ft² (user-typed rates)Estrazione commercialeApriQ = L_hood × CFM/ft (wall canopy 200/300/400/550 by duty)Cappa cucina proApriQ_tot = dryer + hood + baths; makeup if hood>400 or dryer>200Estrazione asciugatriceApriCFM = A × (CFM/ft²) × (H/8); NFA = CFM/750; window = CFM/750Ventilatore per tutta la casaApriCFM = (A × H) / minutes; 2 min = 30 ACH, 3 min = 20 ACHRaffrescatore evaporativoApriCFM = attic floor × 0.7 (dark or steep × 0.805); intake = CFM / 300Ventilatore del sottotettoApriQ/person = G / ((C_in − C_out)/10^6)CO₂ in CFMApriQ = 0.03 A + 7.5 (N_br + 1); q_recovered = 1.08 × Q × ΔT × εCalore ERV/HRVApri
Canale
equal-friction d = (0.109136 × Q^1.9 / f)^(1/5.02); also A = Q/VSezione canaleApriV = Q / AVelocità in canaleApriDe = 1.30 (a b)^0.625 / (a + b)^0.25 (Huebscher)Circolare equivalenteApriΔP/L from user friction rate × length, or Darcy-Weisbach sketchPerdite distribuiteApriΔP = C × (ρ/2) V²Perdite localizzateApriL_center = offset / sin θ; heel-throat from geometryOffset canaleApriESP ≈ Σ ΔP_duct + Σ ΔP_fit + ΔP_coil/filter (user terms)Pressione staticaApriΔP = f × TELLunghezza equivalenteApriAR = a/b; area held, De from HuebscherRapporto d’aspettoApriACFM = SCFM × (T_act/T_std) × (P_std/P_act)SCFM in ACFMApriρ = P / (R T) dry-air sketch; altitude optionalDensità dell’ariaApriA_free = Q / V_face; A_nominal = A_free / free_area_fracGriglia di ripresaApriA_free = Q / V_face; A_nom = A_free / FA; stock register ≥ A_nomBocchetta di mandataApriASP = ESP − ΣΔP_comp; FR = ASP × 100 / TEL (in. w.c./100 ft)Attrito da ESPApriL ≥ max(|W1−W2|,|H1−H2|)/2 / tan(θ_wall)Lunghezza riduzioneApri
Ventilatore
Q₂/Q₁ = N₂/N₁; P₂/P₁ = (N₂/N₁)²; W₂/W₁ = (N₂/N₁)³Leggi dei ventilatoriApriW = Q ΔP / η (consistent units)Potenza ventilatoreApriQ_net = Q_fan × (1 − derate)Derating filtroApriQ = V_cap × A_openingVelocità di catturaApriQ = V_face × A_openCabina di verniciaturaApriQ ≈ Q_nom × √(SP_act / SP_nom) (fan-law sketch — not a catalog curve)Portata vs staticaApri
Calore
q_s = 1.08 × CFM × ΔT (IP, std air); SI: q_s ≈ 1.21 × L/s × ΔT_KCalore sensibileApriq_l = 0.68 × CFM × ΔW_gr (IP, grains)Calore latenteApriT_m = (Q1 T1 + Q2 T2) / (Q1 + Q2)Temperatura miscelaApriCFM = q_s / (1.08 × ΔT)BTU in CFMApritons = BTU/h / 12,000Tonnellate frigorifereApriCFM = tons × (cfm/ton) (user 350–450)CFM per tonApritons ≈ A_floor / ft²-per-ton (rule of thumb — not Manual J)Taglia climatizzatoreApriq ≈ A × U-factor-like × ΔT or BTU/h·ft² × ACarico di riscaldamentoApriInput = Load / AFUETaglia fornaceApriCapacity ≥ max(cooling, heating) with user factorsTaglia pompa di caloreApriBTU/h ≈ A × BTU/h·ft² (room rule of thumb)BTU splitApritons = GPM × ΔT / 24 (water, IP)Potenza chillerApriq = 1.08 CFM ΔT + 0.68 CFM ΔW_grCarico di rinnovoApriIntersect load line q = k (T_in − T_out) with capacity linePunto di equilibrio PdCApriq = 1.08 × CFM × (T_supply − T_out) × shareRiscaldamento rinnovoApriΔT = T_s − T_r; CFM = output / (1.08 × ΔT); output = input × AFUESalto termico caldaia ariaApriq = SHGC × A × I × (1 − shade)SHGC finestraApriW = BTU/h / EER; kWh = W/1000 × hours × duty; COP = EER / 3.412Costo del condizionatoreAprifree in² each = input / rate; gross = free / free-area; volume = 50 ft³ per 1,000 BTU/hApertura aria di combustioneAprielectric ft = (BTU/h / 3.412) / (W/ft); hydronic ft = BTU/h / (BTU/h·ft)Lunghezza del battiscopaApriW = area × W/ft² × (1 + 0.125 × feet over 8); BTU/h = W × 3.412; ft = W / 250Battiscopa dalla stanzaApri
Umidità
e_s = 6.112 exp(17.62 t / (243.12 + t)); W = 0.622 e / (P − e)PsicrometriaApriMagnus inverse from e = RH/100 × e_s(t_db)Punto di rugiadaApriIterated from enthalpy / psychrometric identityBulbo umidoApriRH = e / e_s(t_db) from DB+DP or DB+WBUmidità relativaAprih ≈ 1.006 t + W (2501 + 1.86 t) kJ/kg, t in °CEntalpiaApriW = 0.622 e / (P − e)Rapporto di umiditàApripints/day ≈ ρ Q ΔW × 24h (converted)DeumidificatoreApriQ_OA ≈ 0.48 CFM/ft² × A_water (62.1-style talk; sketch)Piscina copertaAprisingle ≥ 3/4 in; manifold bands by combined tons; slope 1/8 in/ftScarico condensaApriGPD = CFM × 60 × 0.075 × Δgrains/7000 × 24 / 8.34Umidificatore gal/gApriBF = (T_leave − ADP) / (T_enter − ADP); CF = 1 − BFFattore di bypassApri
Acqua
q = 500 × GPM × ΔT (water, IP)GPM in BTUApriGPM = BTU/h / (k × ΔT); water k = 500, 30% PG ≈ 480, 50% PG ≈ 450Portata al glicoleApriv = 0.4085 GPM / ID²; pick Type L copper at ≤ 4 fpsTubo idronicoApriH ≈ lift + Σ friction + fittings (user)Prevalenza pompaAprigal = L × gal/ft + emitters + boiler; glycol = gal × % / 100Volume impiantoApriV_e ≈ V_sys × e; V_t ≈ V_e / (1 − P1/P2)Vaso di espansioneApriInput = Load / ηTaglia caldaiaApriratio = (Tdesign − Tmild) / (OAoff − OAdesign); T = Tmild + ratio × (OAoff − OAnow)Reset esternoApriMakeup ≈ evaporation + blowdown + driftReintegro torre evaporativaAprihf/100 ft = 0.2083 (100/C)^1.852 Q^1.852 / d^4.8655Perdite di carico tuboApriV_gal = t_min × (Q_min − Q_load) / (500 × ΔT)PufferApriBTU = gal × 8.34 × ΔT; output = BTU / hours; input = output / ηRiscaldatore per piscinaApriBTU = gal × 8.33 × ΔT; BTU/h = BTU / hours × climate × exposure × cover; gas input = BTU/h / ηPerdite della vascaApriL = A × 12 / spacing; loops = ceil(L / (L_max − 2 leaders))Circuiti a pavimentoApriBTU/h = area × BTU/h·ft²; tube = area × 12 / spacing; loops = ceil(tube / 250)Scioglimento neveApri