Free Buffer tank volume calculator. V_gal = t_min × (Q_min − Q_load) / (500 × ΔT), then subtract water you already own. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
Ranking buffer-tank calculators (Caleffi / boiler OEM FAQ overlap) use the same thermal mass identity: gallons = minutes × (minimum boiler output − smallest zone load) / (500 × tank ΔT). Defaults 10 minutes and 20 °F swing. 40,000 − 15,000 over 10 min / 20 °F = 25 gallons is the worked set they share. Existing piping gallons subtract from the buy size. Modulation/turndown is how Q_min is born — type it, do not guess 100% of nameplate on a 5:1 mod-con.
It is not an expansion tank (air cushion) and not a DHW cylinder.
Expansion-tank sizes the acceptance volume for heat-up. This page sizes extra water so a low-mass boiler can stay on for ten minutes.
Related calculators on this site:
Type minimum firing output, smallest zone, minutes, ΔT, existing gallons. Example is 40k / 15k / 10 min / 20 °F.
Q_min BTU/h, smallest zone BTU/h, minutes, ΔT °F, existing gallons.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
V = t × (Q_min − Q_load) / (500 × ΔT);
Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 40 kBTU min fire, 15 kBTU zone, 10 min, 20 °F.
2) Cast-iron loop that already holds 40 gallons — buy zero.
3) Heat-pump buffer with Q_load = 0 while charging.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
(40,000 − 15,000) × 10 / (500 × 20) = 25 gal
existing 0 → buy 25 gal (next stock 30)
500 is GPM·ΔT per hour. Minutes already sit in the numerator, so 500 is the ranking shortcut. 8.33 × ΔT × hours is identical.
Nameplate ÷ turndown. A 100k with 5:1 is 20k, not 100k.
Then the tank absorbs the whole fire. Heat-pump charging examples do this.
OEM minimum on-time. 10 is the default those pages share; anti-short-cycle settings may want more.
How far you let the tank walk. Tighter control wants more gallons.
Still needed. Buffer is thermal mass; expansion is air volume for density change.
Composite of ranking buffer identities (500 form and 8.33×ΔT form are the same: 500 = 8.33 × 60). Hydraulic separator volume counts as existing water.
Estimate only for buffer tank volume. OEM min-cycle time and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.