公式
與工具相同。
空氣
CFM = ACH × Volume / 60換氣次數轉 CFM開啟required = max(50 CFM code floor, HVI area or fixtures, 8 ACH); buy next common fan浴室排風扇開啟Q = max(100 CFM, 100 or 150 CFM/ft × width, BTU/h ÷ 100); flag makeup air if Q > 400排油煙機風量開啟Q_vent = 0.03 A_floor + 7.5 (N_br + 1) (ASHRAE 62.2 form, IP)ASHRAE 62.2開啟V_bz = Rp × Pz + Ra × Az (ASHRAE 62.1 breathing-zone form)ASHRAE 62.1 外氣開啟if Q_exh > 400 CFM then Q_mu ≈ Q_exh, else 0 (IRC talk; not Q_exh − 400)補風開啟CFM = ACH × V / 60 or CFM = cfm/ft² × A車庫排風開啟A_net ≈ A_attic / 150 (or /300); split 50/50 intake/exhaust NFA in in²閣樓通風開啟CFM = ACH_ISO × V / 60 (ACH from user ISO class pick or custom)潔淨室換氣開啟Q = V × exchanges/min × (1 + filter%) × lights (1/min is the common tent sketch)種植帳風量開啟ACH = CADR × 60 / V; also CADR_5ACH = V × 5 / 60CADR 換氣開啟ACH_nat ≈ ACH50 / N; CFM_nat ≈ CFM50 / N (N chips 20/16/13)ACH50 轉自然換氣開啟CFM = ACH × V / 60 or CFM = cfm/ft² × A停車庫風量開啟Q_sys = tons × CFM/ton; Q_room = Q_sys × (A×f) / Σ(A×f)房間分風量開啟Q = n × CFM/unit or Q = A × CFM/ft² (user-typed rates)商用排風開啟Q = L_hood × CFM/ft (wall canopy 200/300/400/550 by duty)商用廚房煙罩開啟Q_tot = dryer + hood + baths; makeup if hood>400 or dryer>200烘衣排風與補風開啟CFM = A × (CFM/ft²) × (H/8); NFA = CFM/750; window = CFM/750整屋風扇開啟CFM = (A × H) / minutes; 2 min = 30 ACH, 3 min = 20 ACH蒸發式冷風機開啟CFM = attic floor × 0.7 (dark or steep × 0.805); intake = CFM / 300閣樓風扇開啟Q/person = G / ((C_in − C_out)/10^6)二氧化碳換算風量開啟Q = 0.03 A + 7.5 (N_br + 1); q_recovered = 1.08 × Q × ΔT × εERV/HRV 回收熱開啟
風管
equal-friction d = (0.109136 × Q^1.9 / f)^(1/5.02); also A = Q/V風管尺寸開啟V = Q / A風管風速開啟De = 1.30 (a b)^0.625 / (a + b)^0.25 (Huebscher)當量圓管開啟ΔP/L from user friction rate × length, or Darcy-Weisbach sketch風管摩擦開啟ΔP = C × (ρ/2) V²管件損失開啟L_center = offset / sin θ; heel-throat from geometry風管偏移開啟ESP ≈ Σ ΔP_duct + Σ ΔP_fit + ΔP_coil/filter (user terms)靜壓開啟ΔP = f × TEL當量長度開啟AR = a/b; area held, De from Huebscher高寬比開啟ACFM = SCFM × (T_act/T_std) × (P_std/P_act)SCFM 轉 ACFM開啟ρ = P / (R T) dry-air sketch; altitude optional空氣密度開啟A_free = Q / V_face; A_nominal = A_free / free_area_frac回風口尺寸開啟A_free = Q / V_face; A_nom = A_free / FA; stock register ≥ A_nom送風風口尺寸開啟ASP = ESP − ΣΔP_comp; FR = ASP × 100 / TEL (in. w.c./100 ft)可用靜壓摩擦率開啟L ≥ max(|W1−W2|,|H1−H2|)/2 / tan(θ_wall)風管變徑長度開啟
風機
熱負荷
q_s = 1.08 × CFM × ΔT (IP, std air); SI: q_s ≈ 1.21 × L/s × ΔT_K顯熱開啟q_l = 0.68 × CFM × ΔW_gr (IP, grains)潛熱開啟T_m = (Q1 T1 + Q2 T2) / (Q1 + Q2)混合風溫開啟CFM = q_s / (1.08 × ΔT)BTU 轉 CFM開啟tons = BTU/h / 12,000冷噸開啟CFM = tons × (cfm/ton) (user 350–450)每噸風量開啟tons ≈ A_floor / ft²-per-ton (rule of thumb — not Manual J)冷氣噸數粗算開啟q ≈ A × U-factor-like × ΔT or BTU/h·ft² × A熱負荷粗算開啟Input = Load / AFUE瓦斯爐容量開啟Capacity ≥ max(cooling, heating) with user factors熱泵容量開啟BTU/h ≈ A × BTU/h·ft² (room rule of thumb)分離式 BTU開啟tons = GPM × ΔT / 24 (water, IP)冰水主機噸數開啟q = 1.08 CFM ΔT + 0.68 CFM ΔW_gr外氣負荷開啟Intersect load line q = k (T_in − T_out) with capacity line熱泵平衡點開啟q = 1.08 × CFM × (T_supply − T_out) × share補風加熱開啟ΔT = T_s − T_r; CFM = output / (1.08 × ΔT); output = input × AFUE爐溫升開啟q = SHGC × A × I × (1 − shade)窗戶 SHGC 得熱開啟W = BTU/h / EER; kWh = W/1000 × hours × duty; COP = EER / 3.412冷氣運轉費用開啟free in² each = input / rate; gross = free / free-area; volume = 50 ft³ per 1,000 BTU/h燃燒空氣開口開啟electric ft = (BTU/h / 3.412) / (W/ft); hydronic ft = BTU/h / (BTU/h·ft)踢腳板散熱器長度開啟W = area × W/ft² × (1 + 0.125 × feet over 8); BTU/h = W × 3.412; ft = W / 250按房間算踢腳板開啟
濕度
e_s = 6.112 exp(17.62 t / (243.12 + t)); W = 0.622 e / (P − e)焓濕開啟Magnus inverse from e = RH/100 × e_s(t_db)露點開啟Iterated from enthalpy / psychrometric identity濕球開啟RH = e / e_s(t_db) from DB+DP or DB+WB相對濕度開啟h ≈ 1.006 t + W (2501 + 1.86 t) kJ/kg, t in °C焓開啟W = 0.622 e / (P − e)含濕量開啟pints/day ≈ ρ Q ΔW × 24h (converted)除濕機品脫開啟Q_OA ≈ 0.48 CFM/ft² × A_water (62.1-style talk; sketch)室內泳池通風開啟single ≥ 3/4 in; manifold bands by combined tons; slope 1/8 in/ft冷凝水管徑開啟GPD = CFM × 60 × 0.075 × Δgrains/7000 × 24 / 8.34加濕加侖/日開啟BF = (T_leave − ADP) / (T_enter − ADP); CF = 1 − BF盤管旁通係數開啟
水側
q = 500 × GPM × ΔT (water, IP)GPM 轉 BTU開啟GPM = BTU/h / (k × ΔT); water k = 500, 30% PG ≈ 480, 50% PG ≈ 450乙二醇流量開啟v = 0.4085 GPM / ID²; pick Type L copper at ≤ 4 fps水管管徑開啟H ≈ lift + Σ friction + fittings (user)泵揚程開啟gal = L × gal/ft + emitters + boiler; glycol = gal × % / 100系統容積開啟V_e ≈ V_sys × e; V_t ≈ V_e / (1 − P1/P2)膨脹水箱開啟Input = Load / η鍋爐容量開啟ratio = (Tdesign − Tmild) / (OAoff − OAdesign); T = Tmild + ratio × (OAoff − OAnow)室外重置開啟Makeup ≈ evaporation + blowdown + drift冷卻塔補水開啟hf/100 ft = 0.2083 (100/C)^1.852 Q^1.852 / d^4.8655水管沿程阻力開啟V_gal = t_min × (Q_min − Q_load) / (500 × ΔT)緩衝水箱容積開啟BTU = gal × 8.34 × ΔT; output = BTU / hours; input = output / η泳池加熱器開啟BTU = gal × 8.33 × ΔT; BTU/h = BTU / hours × climate × exposure × cover; gas input = BTU/h / η泳池熱損失開啟L = A × 12 / spacing; loops = ceil(L / (L_max − 2 leaders))地暖回路開啟BTU/h = area × BTU/h·ft²; tube = area × 12 / spacing; loops = ceil(tube / 250)融雪負荷開啟