Latent heat Calculator

Free Latent heat Calculator. latent cooling (or humidification) rate from airflow and a humidity-ratio difference. Runs in your browser; not a permit or a Manual J.

Updates in this browser · not a mechanical permit


Formula

Identity
q_l = 0.68 × CFM × ΔW_gr (IP, grains of moisture per lb dry air)
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

This page converts latent cooling (or humidification) rate from airflow and a humidity-ratio difference. It is the Latent heat tool in the heat group on ACH Calculator.

It is not a dehumidifier pint chart by itself (see dehumidifier) or an enthalpy wheel effectiveness model. If you need those, open a related tool instead of stretching this identity.

The identity on screen is q_l = 0.68 × CFM × ΔW_gr (IP, grains of moisture per lb dry air). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.

Related calculators on this site:

How to use it

Use the fields that match the job: CFM, W_in and W_out in gr/lb or g/kg, or RH pairs via a note to psychrometric. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

q_l = 0.68 × CFM × ΔW_gr (IP, grains of moisture per lb dry air)

Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) Coil taking 20 gr/lb out of 400 CFM.

2) Humidifier adding steam.

3) Pool evaporation load talk.

If the job is life-safety, sterile, or listed equipment, stop here and use the specification.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

The Example button uses this set:

400 CFM

ΔW=20 gr/lb

q_l = 0.68×400×20 = 5440 BTU/h

Work the same arithmetic on paper; the live result should match within rounding.

FAQ

0.68?

Comes from h_fg ≈ 1061 BTU/lb and 7000 gr/lb: 60/7000×1061 ≈ 0.68. It assumes standard air mass flow.

gr/lb vs g/kg?

1 g/kg = 7 gr/lb approximately (actually 7.0). Toggle units.

Need psychrometric first?

Yes if you only have DB/RH. Open psychrometric, copy W.

SHR?

SHR = q_s / (q_s+q_l). Not a third formula.

SI?

q_l (kW) ≈ 3.0 × m_da (kg/s) × ΔW (g/kg) with h_fg ~2501 kJ/kg — the page shows the SI line.

Condensate GPM?

Mass of water = CFM × ρ × ΔW. Separate from q_l but related.

References

Primary identity: q_l = 0.68 × CFM × ΔW_gr (IP, grains of moisture per lb dry air). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.

Disclaimer

Estimate only for Latent heat. Adopted mechanical codes, OEM curves and a licensed designer prevail.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.