Free ASHRAE 62.1 OA Calculator. breathing-zone outdoor air from 62.1 people and area rates you type (Rp, Ra, Pz, Az). Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts breathing-zone outdoor air from 62.1 people and area rates you type (Rp, Ra, Pz, Az). It is the ASHRAE 62.1 OA tool in the air group on ACH Calculator.
It is not 62.2 dwellings, a cleanroom ACH table, or a full 62.1 multi-zone VAV spreadsheet. If you need those, open a related tool instead of stretching this identity.
The identity on screen is V_bz = Rp × Pz + Ra × Az. Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: People Pz, area Az, Rp (CFM/person), Ra (CFM/ft²). Preset chips for office / classroom / retail as examples only. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
V_bz = Rp × Pz + Ra × Az
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) Office 10 people, 1,000 ft², Rp=5, Ra=0.06 → 110 CFM.
2) Classroom Rp=10, Ra=0.12.
3) Retail with a high area component.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
Pz=10
Az=1000 ft²
Rp=5, Ra=0.06
V_bz = 5×10 + 0.06×1000 = 110 CFM
Work the same arithmetic on paper; the live result should match within rounding.
They are rounded teaching values. ASHRAE 62.1 Table 6-1 (numbering varies by year) is copyrighted. Type the Rp/Ra from your licensed copy.
This is V_bz. Multi-zone VAV uses Ev, diversity and system-level OA. That spreadsheet is not this page.
Both are required in the 62.1 form. People-only CFM under-ventilates large low-occupancy floors.
Use whole-house (62.2), not this page.
Rp in L/s·person and Ra in L/s·m² are the SI 62.1 form. Toggle units.
No. Exhaust and makeup are separate. OA can be larger than exhaust or vice versa.
Primary identity: V_bz = Rp × Pz + Ra × Az. Interpret it with the sources listed below, not as a photocopy of a copyrighted table.
Estimate only for ASHRAE 62.1 OA. Adopted mechanical codes, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.