Free Supply register size calculator. Stock floor or ceiling register from room CFM, face velocity and free-area share. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page sizes a supply register the way ranking calculators overlap: free area = CFM / face FPM, nominal face = free area / free-area fraction, then the next common floor or ceiling size. Face-velocity chips sit at 400–700 FPM because that is the band those pages all publish; 500 FPM is the mid default. Max CFM per register (180) is the comfort split they use, not a code table.
It is not Manual T throw software and not a Hart & Cooley catalog. Neck NC and spread come from the submittal.
Return-grille uses 300 FPM stock and larger filter-grille sizes. This page defaults 65% free area and 500 FPM and keeps floor vs ceiling stock lists separate.
Related calculators on this site:
Pick floor or ceiling/sidewall, type room CFM, leave 500 FPM and 65% unless the submittal says otherwise. Example loads 120 CFM. Next bar carries CFM into the room-split and duct-size pages.
CFM, floor vs ceiling, face FPM chips 400/500/600/700, free area %, max CFM per register.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
registers = ceil(Q / Q_max);
Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 120 CFM bedroom floor boot at 500 FPM, 65% free.
2) Ceiling register that needs 600 FPM throw.
3) Split a 360 CFM living room across two faces.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
Q=120 CFM, floor, 500 FPM, 65%, max 180
1 register; A_free=34.6 in²; A_nom=53.2 in²
next floor stock 4×14; V_act near 475 FPM
Ranking pages put floor registers around 400–600 FPM (they dump up a wall) and ceiling/sidewall 500–700 FPM so the jet throws. Below about 350 FPM a ceiling face dumps.
Stamped residential supplies with a damper sit near 60–70%. Bar-type 75–80%. Type the submittal.
One per 100–180 CFM is the overlap. This page uses 180 as a conservative max; drop it to 120 for quieter rooms.
Same identity, different velocity and stock list. Returns are quieter at 300 FPM; supplies need throw.
Catalog. This page only flags actual face velocity after the stock pick.
Face velocity uses the grille face. The collar is a duct-velocity problem.
Composite of ranking register calculators: A_free = Q/V, 65% stamped free area, 400–600 floor / 500–700 ceiling FPM, 100–180 CFM per face. Not a photocopy of any one site.
Estimate only for supply register size. Adopted codes, OEM free-area sheets and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.