Supply register size Calculator

Free Supply register size calculator. Stock floor or ceiling register from room CFM, face velocity and free-area share. Runs in your browser; not a permit or a Manual J.

Updates in this browser · not a mechanical permit


Formula

Identity
registers = ceil(Q / Q_max); A_free = Q_each / V; A_nom = A_free / FA; stock ≥ A_nom
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

This page sizes a supply register the way ranking calculators overlap: free area = CFM / face FPM, nominal face = free area / free-area fraction, then the next common floor or ceiling size. Face-velocity chips sit at 400–700 FPM because that is the band those pages all publish; 500 FPM is the mid default. Max CFM per register (180) is the comfort split they use, not a code table.

It is not Manual T throw software and not a Hart & Cooley catalog. Neck NC and spread come from the submittal.

Return-grille uses 300 FPM stock and larger filter-grille sizes. This page defaults 65% free area and 500 FPM and keeps floor vs ceiling stock lists separate.

Related calculators on this site:

How to use it

Pick floor or ceiling/sidewall, type room CFM, leave 500 FPM and 65% unless the submittal says otherwise. Example loads 120 CFM. Next bar carries CFM into the room-split and duct-size pages.

CFM, floor vs ceiling, face FPM chips 400/500/600/700, free area %, max CFM per register.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

registers = ceil(Q / Q_max); A_free = Q_each / V; A_nom = A_free / FA; stock ≥ A_nom

Reject zero or negative lengths, areas, flows, pressures and temperatures. This is a ranking-composite sketch, not a permit.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) 120 CFM bedroom floor boot at 500 FPM, 65% free.

2) Ceiling register that needs 600 FPM throw.

3) Split a 360 CFM living room across two faces.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

The Example button uses this set:

Q=120 CFM, floor, 500 FPM, 65%, max 180

1 register; A_free=34.6 in²; A_nom=53.2 in²

next floor stock 4×14; V_act near 475 FPM

FAQ

Floor or ceiling velocity?

Ranking pages put floor registers around 400–600 FPM (they dump up a wall) and ceiling/sidewall 500–700 FPM so the jet throws. Below about 350 FPM a ceiling face dumps.

Why 65% free area?

Stamped residential supplies with a damper sit near 60–70%. Bar-type 75–80%. Type the submittal.

How many registers?

One per 100–180 CFM is the overlap. This page uses 180 as a conservative max; drop it to 120 for quieter rooms.

Same as a return?

Same identity, different velocity and stock list. Returns are quieter at 300 FPM; supplies need throw.

Throw data?

Catalog. This page only flags actual face velocity after the stock pick.

Neck vs face?

Face velocity uses the grille face. The collar is a duct-velocity problem.

References

Composite of ranking register calculators: A_free = Q/V, 65% stamped free area, 400–600 floor / 500–700 ceiling FPM, 100–180 CFM per face. Not a photocopy of any one site.

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.