For a given fan on a given system curve, with density held still: Q₂/Q₁ = N₂/N₁, P₂/P₁ = (N₂/N₁)², W₂/W₁ = (N₂/N₁)³. A fan at 1,000 rpm moving 2,000 CFM, slowed to 900 rpm, is about 1,800 CFM. Pressure drops by 0.81×. Power drops by 0.73×. The cube law is why a small speed increase overloads a motor.
The laws fail when you change the wheel, the housing, the duct system, or the density a lot (hot relief air, altitude). They also fail as a substitute for “the job is at 0.8 in instead of 0.5 in.” That is a different operating point on a curve — use fan actual only as a square-root sketch, then read the catalog.
What to open
Fan laws for speed ratios. Fan BHP for BHP = CFM × SP / (6356 η) and the next NEMA motor. Air density if altitude or temperature moved.
FAQ
Same fan, new duct?
System curve changed. Laws do not apply cleanly. Need a new operating point.
VFD minimum speed?
Motors, bearings and the driven load set a floor. Laws do not.
Density correction?
Affinity laws have density forms. This page keeps density constant unless you change it elsewhere.
Forward-curve versus airfoil?
Laws still hold as ratios; catalog stall and inefficiency do not transfer.
Noise?
Not a fan-law output. Velocity and blade tone live on the duct-velocity guide.
Limits
Not a fan-selection program and not a vibration analysis.
Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.