ΔT °FGPM for 100,000 BTU/h
1020
2010
306.67

Open GPM to BTU for any load. 10 GPM at 4 fps is about 1 in Type L on hydronic pipe. Glycol: type a constant under 500.

FAQ

Chilled 10 °F?

Common. 2.4 GPM/ton because tons = GPM ΔT / 24.

Boiler 20 °F?

Common reset-era talk. Condensing boilers may use other ΔT.

Steam?

Not this table.

50% glycol?

Expect more GPM for the same q. Confirm cp.

Why 500 not 8.33?

8.33 is lb/gal; 500 already includes 60 min/h.

Limits

Not a pump affinity table.

Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.