| ΔT °F | GPM for 100,000 BTU/h |
|---|---|
| 10 | 20 |
| 20 | 10 |
| 30 | 6.67 |
Open GPM to BTU for any load. 10 GPM at 4 fps is about 1 in Type L on hydronic pipe. Glycol: type a constant under 500.
FAQ
Chilled 10 °F?
Common. 2.4 GPM/ton because tons = GPM ΔT / 24.
Boiler 20 °F?
Common reset-era talk. Condensing boilers may use other ΔT.
Steam?
Not this table.
50% glycol?
Expect more GPM for the same q. Confirm cp.
Why 500 not 8.33?
8.33 is lb/gal; 500 already includes 60 min/h.
Limits
Not a pump affinity table.
Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.