Pool Heat Loss Calculator

Free pool heat-loss calculator. BTU = gallons × 8.33 × temperature rise, divided by the heat-up hours, then multiplied by climate, exposure, and cover. Runs in your browser; not a permit.

Updates in this browser · not a mechanical permit


Formula

Identity
BTU = gal × 8.33 × ΔT; into the water = BTU / hours × climate × exposure × cover; gas input = into the water / η
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

This page estimates the heat to raise a pool. Total heat = gallons × 8.33 × the rise, then divided by the hours you want that rise to take. Cold multiplies by 1.5, warm by 0.9, and a fully exposed outdoor pool by 1.3. A cover cuts about 50 to 70 percent of the heating, so the chip uses one half. A gas heater delivers about 84 percent of its input into the water, so input is the water-side rate divided by efficiency.

Not a solar-panel area, and not a heat-pump COP. The existing pool-heater page is the same water rise with no climate, wind, or cover.

Leave climate, exposure, and cover at 1 to match the plain water sum. 1.5 is cold, 0.9 is warm, 1.3 is exposed, 0.5 is a cover.

Related calculators on this site:

How to use it

Type gallons, the rise, hours, and efficiency. Chips set the three factors. Example is 20,000 gal, 10°F, 24 hours, all factors 1, 84 percent.

Gallons, ΔT °F, heat-up hours, climate, exposure, cover, efficiency %.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

BTU = gal × 8.33 × ΔT; into the water = BTU / hours × climate × exposure × cover; gas input = into the water / η

Gallons, rise, hours, and efficiency must be positive. Factors default to 1. This is the heat-up multiplied by climate, exposure, and cover. It is not a surface-evaporation model with wind speed in miles per hour.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) 20,000 gal, 10°F, 24 h, factors at 1.

2) The same pool, cold and exposed: 1.5 and 1.3.

3) The same pool with the cover chip at 0.5.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

The example is 20,000 gallons, a 10°F rise, 24 hours, and all three factors at 1:

20,000 × 8.33 × 10 = 1,666,000 BTU

1,666,000 / 24 = 69,417 BTU/h into the water. Gas input at 84 percent is 82,639 BTU/h.

FAQ

Why 8.33?

About 8.33 pounds of water per gallon. The other heat-up page on this site uses 8.34. The difference is under 1 percent.

What are 1.5, 0.9, and 1.3?

1.5 is a cold climate, 0.9 is a warm climate, and 1.3 is a fully exposed outdoor pool. Moderate weather and a sheltered pool stay at 1.

Why is the cover 0.5?

A cover cuts about 50 to 70 percent of the heating. The chip uses the 50 percent end, so the hourly rate is cut in half.

Why divide by 0.84?

A gas heater delivers about 84 percent of its input into the water. If a heat-pump nameplate is already output, type 100.

Where is the surface area?

This page uses climate and exposure multipliers. It does not ask for water surface area or a wind-speed coefficient.

Same as the other pool page?

The other page is gallons × 8.34 × rise / hours / efficiency, with no climate, exposure, or cover. Use this page when those three matter.

References

Water uses 8.33 pounds per gallon. Cold is about +50 percent, warm about −10 percent, a fully exposed outdoor pool about +30 percent. Gas delivers about 84 percent into the water. A cover is taken at the 50 percent end of a 50 to 70 percent cut.

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.

Disclaimer

Estimate only. A cover, the wind, and the heater listing move the real hours.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.