Free Hydronic pipe size Calculator. pipe inside diameter from GPM and a target velocity (or friction as a user rate). Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts pipe inside diameter from GPM and a target velocity (or friction as a user rate). It is the Hydronic pipe size tool in the water group on ACH Calculator.
It is not a copper Type L pressure table, a steel schedule reprint, or a full Hazen-Williams network. If you need those, open a related tool instead of stretching this identity.
The identity on screen is A = Q / V; for IP gpm & fps: d_in ≈ √(GPM / (2.45 V)). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: GPM, velocity chips 2–8 fps, result nominal ID and fps actual. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
v = 0.4085 GPM / ID²;
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 10 GPM at 4 fps.
2) Boiler header.
3) Too-fast noise in copper.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
10 GPM
4 fps
Type L 1 in (ID 1.025 → about 3.9 fps)
Work the same arithmetic on paper; the live result should match within rounding.
A common copper hydronic band. Large mains may be faster; branches quieter.
Type ft/100 ft if you prefer; velocity is the default.
1 in Type L copper ID is not 1.00 in. This sketch uses ID you type or a nominal chip.
Raises friction. Not a full Moody chart.
Closed loops ignore elevation in pump head except for fill/expansion. Open systems do not.
pump-head.
Primary identity: A = Q / V; for IP gpm & fps: d_in ≈ √(GPM / (2.45 V)). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.
Estimate only for Hydronic pipe size. Adopted mechanical codes, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.