Pool Heater Size Calculator

Free pool heater calculator. Heat = gallons × 8.34 × °F rise. Output per hour divides by the heat-up time. Gas input divides by efficiency. Runs in your browser; not a permit.

Updates in this browser · not a mechanical permit


Formula

Identity
BTU = gal × 8.34 × ΔT; output = BTU / hours; fuel input = output / η
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

Ranking pool-heater calculators that size from volume use one identity: a US gallon of water weighs 8.34 lb, and one BTU raises one pound by 1 °F. Heat is gallons × 8.34 × the rise. Divide by the hours you allow, then divide by efficiency when the nameplate is fuel input. 15,000 gallons, 10 °F and 8 hours is a worked set those pages share. A heat pump whose label is already heat into the water uses 100% here.

Not a surface-evaporation model and not a cover. Another ranking method is pool area × (pool temperature − coldest-month air) × 12 BTU/h, for about 1 °F per hour in a light wind. This page is the volume heat-up.

The indoor-pool page is dehumidifier airflow. This page is the heater that warms the water.

Related calculators on this site:

How to use it

Type gallons, the rise, the hours and the efficiency. Example is 15,000 gal, 10 °F, 8 hours, 82%.

Gallons, ΔT °F, heat-up hours, efficiency %.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

BTU = gal × 8.34 × ΔT; output = BTU / hours; fuel input = output / η

Gallons, rise, hours and efficiency must be positive. Heaters are sold in steps; buy the step above the input, not the raw number. Wind, sun and a cover move the real time.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) 15,000 gal, 10 °F, 8 hours, 82% gas.

2) The same pool in 4 hours.

3) A heat pump already rated as output, at 100%.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

The Example button uses this set:

15,000 × 8.34 × 10 = 1,251,000 BTU

1,251,000 / 8 = 156,375 BTU/h into the water. At 82% the fuel input is 190,701 BTU/h.

FAQ

Why 8.34?

Pounds in a US gallon. One BTU raises one pound of water by 1 °F.

Why 15,000 gal and 8 hours?

15,000 × 8.34 × 10 = 1,251,000 BTU. Over 8 hours that is 156,375 BTU/h into the water.

Why 82%?

Gas nameplates are usually input. 82% is the efficiency those pages preload. A heat pump rated as output uses 100% here.

What about surface area?

Another ranking method is ft² × (pool − coldest-month air) × 12 BTU/h. This page is the volume heat-up. A cover changes the loss; wind is not in this number.

Which heater do I buy?

Heaters are sold in steps. 190,701 BTU/h of fuel input sits under a 200,000 BTU/h unit on the tables those sites print.

A hot tub?

Same identity. Tubs care more about volume and a short heat-up than about surface area.

References

Composite of ranking pool-heater calculators. 8.34 lb/gal is the shared factor. 15,000 gal, 10 °F, 8 hours and about 82% efficiency is a worked set on those pages. Surface area × ΔT × 12 is the other method, not this one.

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.

Disclaimer

Estimate only for a still pool with no ongoing loss. A cover, wind and the coldest month change the heater you actually need.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.