Air-change and room CFM calculators
Room ACH, bath fans, 62.1/62.2, makeup air and CADR.
Room ACH, bath fans, 62.1/62.2, makeup air and CADR.
This group converts room ACH, bath exhaust, kitchen hoods, ASHRAE 62.2 whole-house air, 62.1 outdoor air, makeup air, CADR, ACH50 and related exhaust sketches into a flow you can take to a fan or a duct.
It is not a duct sizer and not a coil load. Each card is one identity: do not add bath 50 CFM to a 62.2 dwelling rate unless the design says so.
Open ACH to CFM for a box. Open bathroom-fan for IMC-style 50/20. Open whole-house for 62.2, outdoor-air for people+area, kitchen-hood for capture, makeup-air when exhaust is large.
Type the room or occupancy the page asks for. Example on each tool matches that page’s worked section.
Room: CFM = ACH × V / 60. Bath chips: 50 CFM intermittent / 20 continuous. 62.2: Q = (CFA × 0.03) + 7.5(Nbr+1) plus infiltration options. 62.1: Vbz = Rp×Pz + Ra×Az. Hood: Q ≈ 100 CFM per foot or face velocity × area.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Use air tools when the unknown is outdoor air or exhaust CFM. Use duct tools when you already have CFM and need size or pressure.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
12×14×8 ft at 6 ACH → 134.4 CFM on ACH to CFM. A 5×8×8 ft bath at 50 CFM is about 9.4 ACH — the table, not the ACH, usually governs.
A 2,000 ft², 3-bedroom dwelling 62.2 sketch is on whole-house, not on this group’s ACH card.
ACH is a room rate. 62.2 is a dwelling outdoor-air form. They share CFM and almost never the same equation.
A hood captures at the cooktop. Diluting the whole kitchen does not replace capture velocity.
Open makeup-air when several baths plus a hood exceed the local threshold, not for a single 50 CFM fan.
CADR is cleaner CFM for a portable filter, not outdoor air.
ISO class names are discussion ranges, not particle limits. Use the spec.
That page is a ventilation sketch, not a CO-system design.
Exhaust tables and 62.1/62.2 forms are estimates. Adopted code year and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size combustion air, refrigerant charge, fire dampers, medical gas, or electrical conductors.