Sensible, tons, and equipment sketches

1.08, 0.68, 400 CFM/ton, chillers, furnaces — not Manual J.

Heat

Sensible heatSensible heating or cooling rate of an airstream from CFM and dry-bulb difference.Latent heatLatent cooling (or humidification) rate from airflow and a humidity-ratio difference.Mixed-air temperatureMixed-air dry bulb (and optional humidity ratio) from two airstreams, typically OA and return.BTU to CFMRequired airflow from a sensible BTU/h and a temperature difference (inverse of 1.08).Cooling tonsCooling tons from BTU/h or kW, and the reverse.CFM per tonAirflow from cooling tons using the 400 CFM/ton family of rules you can edit.AC sizeA crude residential air-conditioner capacity from floor area — labeled as not Manual J.Heating loadA crude winter heating load from area and a user BTU/h·ft² or a UA×ΔT sketch.Furnace sizeFurnace input and output from a heating load and AFUE (and an optional oversize pickup).Heat-pump sizeA comparison of cooling tons and heating BTU/h so you can see which one governs a heat-pump pick.Mini-split BTUA room-level ductless capacity sketch from area and a BTU/h per square foot chip.Chiller tonnageEvaporator (or condenser) tons from chilled-water flow and ΔT.Ventilation loadOutdoor-air sensible plus latent load from OA CFM and indoor/outdoor psychrometric states.Heat-pump balance pointAn outdoor-temperature balance point from a linear load line and a linear heat-pump capacity line you type with two points each.Makeup-air heatingWinter MAU output q = 1.08 × CFM × (T_supply − T_outdoor) × share.Furnace temperature riseΔT = supply − return; CFM = output / (1.08 × ΔT); check the nameplate 35–65 °F band.Window SHGC heat gainSolar gain q = SHGC × area × irradiance × (1 − shade fraction).AC running costWatts = BTU/h ÷ the efficiency number. Cost = kW × hours × duty × your price.Combustion air openingFree area per opening = input ÷ the rate you pick. Gross opening divides by the louver’s free area.Baseboard lengthElectric feet = (BTU/h ÷ 3.412) ÷ W/ft. Hot-water feet = BTU/h ÷ the element’s BTU/h per foot.Baseboard from the roomWatts = room area × W/ft². Length = watts / 250.

What this calculator does

These tools sketch sensible and latent coil load from CFM and ΔT, mixed-air temperature, 400 CFM/ton, furnace and heat-pump size chips, chiller tons from GPM × ΔT / 24, and a ventilation load.

They are not Manual J, not a bin weather file, and not a selection of listed indoor units. Do not buy tons from a square-foot chip without a load calculation.

How to use it

Open sensible-heat for 1.08 × CFM × ΔT. Open latent for 0.68 × CFM × ΔW. Open cfm-per-ton or cooling-tons for the 400 CFM/ton talk. Open chiller-tonnage when you have evaporator GPM and ΔT.

You need a flow and two temperatures (or a humidity ratio). Equipment chips are rules of thumb, not OEM performance.

Formula, units, and limits

qs (BTU/h) = 1.08 × CFM × ΔT. ql = 0.68 × CFM × Δgrains. Tons ≈ CFM / 400 or GPM × ΔT / 24 on water. Mixed air is a mass-weighted dry-bulb.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Use this group when CFM is known and you want a coil or equipment sketch. Use air tools first if CFM is the unknown.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

800 CFM across a 20 °F dry-bulb drop → 1.08 × 800 × 20 = 17,280 BTU/h sensible ≈ 1.4 tons of sensible only.

40 GPM chilled water at 10 °F ΔT → 40 × 10 / 24 ≈ 16.7 tons. That ignores glycol and fouling.

FAQ

Why 1.08?

1.08 ≈ 0.075 lb/ft³ × 0.24 BTU/lb·°F × 60 min/h for standard air. Override density at altitude.

Is 400 CFM/ton required?

It is a US conventional coil face talk. Humid climates often run lower CFM/ton.

Manual J?

Not here. These pages invert coil identities, they do not take off envelope loads.

Minisplit size?

A chip from floor area, not a manufacturer table.

Balance point?

A heat-pump sketch versus outdoor temperature, not a utility tariff.

Latent without a psych chart?

You still need a humidity-ratio change. Open moisture tools if you only have RH.

References

Disclaimer

Rules of thumb. Nameplate capacity, SHR and a licensed load calc prevail.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size combustion air, refrigerant charge, fire dampers, medical gas, or electrical conductors.