Sensible, tons, and equipment sketches
1.08, 0.68, 400 CFM/ton, chillers, furnaces — not Manual J.
1.08, 0.68, 400 CFM/ton, chillers, furnaces — not Manual J.
These tools sketch sensible and latent coil load from CFM and ΔT, mixed-air temperature, 400 CFM/ton, furnace and heat-pump size chips, chiller tons from GPM × ΔT / 24, and a ventilation load.
They are not Manual J, not a bin weather file, and not a selection of listed indoor units. Do not buy tons from a square-foot chip without a load calculation.
Open sensible-heat for 1.08 × CFM × ΔT. Open latent for 0.68 × CFM × ΔW. Open cfm-per-ton or cooling-tons for the 400 CFM/ton talk. Open chiller-tonnage when you have evaporator GPM and ΔT.
You need a flow and two temperatures (or a humidity ratio). Equipment chips are rules of thumb, not OEM performance.
qs (BTU/h) = 1.08 × CFM × ΔT. ql = 0.68 × CFM × Δgrains. Tons ≈ CFM / 400 or GPM × ΔT / 24 on water. Mixed air is a mass-weighted dry-bulb.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Use this group when CFM is known and you want a coil or equipment sketch. Use air tools first if CFM is the unknown.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
800 CFM across a 20 °F dry-bulb drop → 1.08 × 800 × 20 = 17,280 BTU/h sensible ≈ 1.4 tons of sensible only.
40 GPM chilled water at 10 °F ΔT → 40 × 10 / 24 ≈ 16.7 tons. That ignores glycol and fouling.
1.08 ≈ 0.075 lb/ft³ × 0.24 BTU/lb·°F × 60 min/h for standard air. Override density at altitude.
It is a US conventional coil face talk. Humid climates often run lower CFM/ton.
Not here. These pages invert coil identities, they do not take off envelope loads.
A chip from floor area, not a manufacturer table.
A heat-pump sketch versus outdoor temperature, not a utility tariff.
You still need a humidity-ratio change. Open moisture tools if you only have RH.
Rules of thumb. Nameplate capacity, SHR and a licensed load calc prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size combustion air, refrigerant charge, fire dampers, medical gas, or electrical conductors.