Free Chiller tonnage Calculator. evaporator (or condenser) tons from chilled-water flow and ΔT. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts evaporator (or condenser) tons from chilled-water flow and ΔT. It is the Chiller tonnage tool in the heat group on ACH Calculator.
It is not airside 400 CFM/ton, compressor kW, or glycol without a cp correction. If you need those, open a related tool instead of stretching this identity.
The identity on screen is tons = GPM × ΔT / 24 (water, IP); q = 500 × GPM × ΔT BTU/h. Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: GPM, ΔT °F, fluid chip water/glycol (user cp), result tons and BTU/h. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
tons = GPM × ΔT / 24 (water, IP);
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 240 GPM at 10 °F → 100 tons.
2) Primary loop 12 °F ΔT.
3) Glycol 30% user factor.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
GPM=240
ΔT=10
tons=240×10/24=100
Work the same arithmetic on paper; the live result should match within rounding.
500 × GPM × ΔT / 12,000 = GPM × ΔT / 24. The 500 is 8.33 lb/gal × 60 × 1.0 BTU/lb·°F.
cp and density drop the 500 constant. Type a factor (e.g. 0.9×).
Same identity, different GPM and ΔT.
q(kW) = 4.186 × L/s × ΔT_K for water.
Tower approach is not this. Cooling-tower makeup is another page.
Still has an evaporator GPM. Condenser is air — use the OEM.
Primary identity: tons = GPM × ΔT / 24 (water, IP); q = 500 × GPM × ΔT BTU/h. Interpret it with the sources listed below, not as a photocopy of a copyrighted table.
Estimate only for Chiller tonnage. Adopted mechanical codes, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.